Configurations
Table 1: Configuration Information
Note:
Baffles are always placed in the last section of radiant tube.
Baffles are either aluminized or stainless steel sections 6' long.
When only 6' is required an aluminized steel baffle is installed, except on the WTH-40,000 where a special 6'
stainless steel baffle with a red identification tab must be installed.
When 12' is required, a 6’ stainless steel baffle is inserted first into the end tube followed by another 6’
aluminized baffle. The stainless steel baffle is now closest to the burner.
Part numbers for reference are:
CT045
Baffle Kit, WTH-40,000 BTU/hr only, 6' long, stainless steel with red identification tab.
CT046
Baffle Kit, 6' long, aluminized steel
CT047
Baffle Kit, 12' long aluminized & stainless steel.
*The following Special Configurations are also approved:
80,000 BTU/Hr,
50
’ heat exchanger with no baffle or 6’ aluminized baffle
100,000 BTU/Hr,
50
’ heat exchanger with no baffle or 6’ aluminized baffle
150,000 BTU/Hr,
60
’ heat exchanger with no baffle or 6’ aluminized baffle
The following special configurations are also approved with Premium Heat Exchanger only:
80,000 BTU/Hr,
20
’ heat exchanger with 12’ baffle
100,000 BTU/Hr,
20
’ heat exchanger with 12’ baffle
125,000 BTU/Hr,
30
’ heat exchanger with 12’ baffle
205,000 BTU/Hr,
50' heat exchanger with a 4' baffle at 40', and a 8' baffle at 50'.
Model
* Special Configurations
available
– see below
Rate
(BTU/Hr)
Heat Exchanger Length ft.
(m)
Baffle
ft.
(m)
Minimum
Maximum
WTH-40
40,000
10' (3m)
20' (6m)
6' (1.8m)
WTH-60
60,000
20' (6m)
30' (9m)
6' (1.8m)
WTH-80
80,000
30' (9m)
40' (12m)
12' (3.6m)
WTH-100
100,000
30' (9m)
40' (12m)
12' (3.6m)
WTH-125
125,000
40' (12m)
50' (15m)
6' (1.8m)
WTH-150
150,000
40' (12m)
60' (18m)
6' (1.8m)
WTH-175
175,000
50' (15m)
60' (18m)
-
WTH-205
205,000
60' (18m)
70' (21m)
-