Solar charge inverter V1.0 26
Parameter
no.
Parameter
name
Settings
Description
range is 5S~55S, with a step of 5S. It is valid for
user-defined battery and lithium battery.
14
Battery under
voltage alarm
[14] 22V
default
Battery undervoltage alarm point; when the
battery voltage is lower than the point, an
undervoltage alarm is given, and the output is
not turned off; the setting range is 20V~26V,
with a step of 0.2V. It is valid for user-defined
battery and lithium battery.
15
Battery
discharge limit
voltage
[15] 20V
default
Battery discharge limit voltage; when the
battery voltage is lower than the point, the
output is turned off immediately; the setting
range is 20V~26V, with a step of 0.2V. It is valid
for user-defined battery and lithium battery.
16
Battery
equalization
enable
[16] DIS
Equalizing charge is disabled
[16] ENA
default
Equalizing charge is enabled, only valid for
vented lead-acid battery and sealed lead-acid
battery
17
Battery
equalization
voltage
[17] 29.2V
default
Equalizing charge voltage; setting range:
24V~29.2V, with a step of 0.2V; valid for vented
lead-acid battery and sealed lead-acid battery
18
Battery
equalized time
[18] 120
default
Equalizing charge time; setting range:
5min~900min, with a step of 5 minutes; valid
for vented lead-acid battery and sealed lead-
acid battery
19
Battery
equalized time
out
[19] 120
default
Equalizing charge delay; setting range:
5min~900min, with a step of 5 minutes; valid
for vented lead-acid battery and sealed lead-
acid battery
20
Battery
equalization
interval
[20] 30
default
Equalizing charge derating time, 0~30days,
with a step of 1 day; valid for vented lead-acid
battery and sealed lead-acid battery
21
[21] DIS
Stop equalizing charge immediately.