Mini-VARIO and VARIO Manual Motor Control Switches
Specifications
© 1999 Square D All Rights Reserved
4
3/99
Switch Type
V2
V2
VVD2
VVE2
V3
VZ3
VVD3
VVE3
V4
VZ4
VVD4
VVE4
V5
V6
VZ7
VZ20
VZN05
VZN06
Environment
Conforming to Standards
IEC 947-3
947-5
Approvals
UL, CSA, GL, UL File # E164864 CCN NLRV, CSA File # LR81630 Class 3211 02
Protective Treatment
“TC”
Degree of Protection
with Protection Shroud
IP 20 conforming to IEC 529
Ambient Air Temperature
-4 to +122
°
F (-20 to +50
°
C)
Flame Resistance
960
°
C (1760
°
F) conforming to IEC 695-2-1
Shock Resistance
1/2 Sine Wave = 11ms
Conforming to IEC 68-2-27
30 g
–
Vibration Resistance
10 to 150 Hz
Conforming to IEC 68-2-6
1 g
–
Electrical Characteristics, AC Operation
Rated Operational Voltage (Ue)
V
690
690
690
690
690
690
690
Rated Impact Withstand Voltage (Uimp)
kV
8
8
8
8
8
8
6
Conventional Thermal Currents in Free Air
(Ith) and Rated Uninterrupted (Iu)
A
40
63
80
125
175
12
6
Conventional Thermal Current in Enclosure
(Ithe)
A
32
50
63
100
140
10
4
Rated Operational Power and Current
AC-21A/22A
230 to 690 V
A
40
63
80
125
160
Ie/AC-15
Ie/AC-15
AC-23A
230 V
A (kW)
25.8 (7.5)
50.3 (15)
61.2 (18.5)
71.9 (22)
96.6 (30)
6 A
6 A
240 V
A (kW)
24.8 (7.5)
48.2 (15)
58.5 (18.5)
68 (22)
92.7 (30)
6 A
6 A
400 V
A (kW)
29 (15)
41.5 (22)
57 (30)
68.5 (37)
83 (45)
4 A
4 A
415 V
A (kW)
28 (15)
40 (22)
55 (30)
66 (37)
80 (45)
4 A
4 A
500 V
A (kW)
28.5 (18.5)
44 (30)
54 (37)
64.5 (45)
79 (55)
2 A
2 A
690 V
A (kW)
17.5 (15)
25 (22)
33 (30)
42 (37)
49 (45)
1 A
1 A
Rated Operational Power
AC-3
230/240 V
kW
5.5
11
15
22
30
–
–
400/415 V
kW
11
18.5
22
30
37
–
–
500 V
kW
15
22
30
37
45
–
–
690 V
kW
11
18.5
18.5
30
37
–
–
Intermittent Duty Class
30
30
30
30
30
–
–
Characteristics in Normal
Operating Conditions
Rated Making Capacity
AC-21A/22A/23A (I rms)
A/400 V
400
630
800
1250
1750
–
–
Rated Breaking Capacity
AC-21A/22A/23A (I rms)
A/400 V
320
500
640
1000
1400
–
–
Short-circuit Characteristics
Permissible ms Short Time
Rating (Icw)
A/400 V/1s
480
756
960
1500
2100
–
–
Rated Making Capacity Under
Short-circuit Condition (Icm) I Peak
kA/400 V
1
2.1
2.1
2.8
2.8
–
–
Rated Conditional Short-circuit
Current (I rms)
kA/400 V
10
10
10
10
10
1
1
with a M/g G Fuses
A
50
63
80
125
200
16
1.6