Spyder Robotics Herpstat HP User Manual Download Page 5

Safety Setup 

(menu option)

 

 

From the initial menu screen select Safety Setup using the Plus and Minus button and press Enter.   

 

 

 

Safety Relay:   

This setting determines the operation of the Safety Relay during an error condition.   Once the error condition is 

corrected the device will return to normal operations. 

 

Options: 

 

DISABLED 

This option is the default setting.  Safety relay is not enabled.  

 

ON ANY ERROR 

During an

y error condition it triggers the Safety Relay.  High/Low alarms will also shut off the output. 

 

H-ALARM ONLY 

During a

 High Alarm error condition it triggers the Safety Relay.  Low alarms will beep but will not activate the 

safety relay and power will continue. 

 

The Display 

 

In normal operation the Minus button will toggle between the available displays while the Plus button will 

activate special features of that display.  The Enter button will activate the menu system. 

 

 

   

 

Temperature  Status & Power Output 

This display shows the current temperatures from probe.  If an error occurs a description will be shown instead 

of the output information.  The setting the device is trying to achieve is in parentheses.  When ramping is 

enabled for temperature the value in parentheses will change according to the time based curve. 

 

Special Symbols: 

 

Next to the number of the output an arrow symbol will appear if that output is currently in a ramping session.  A 
right arrow (

) will appear if the ramp is increasing.  A left arrow (

 will appear if the ramp is decreasing.  

 
Next to the number of the output a minus sign (

-

) will appear if a Low Alarm has been breached.  A plus sign 

(

+

) will appear if a High Alarm has been breached. 

 

 

 

 

High Low Status 

This display indicates the highest and lowest temperature level recorded for the probe and the time at which it 

was recorded.  Pressing the + button will reset the High/Low to the current reading. 

 

 

 

System Information 

This display indicates the system time and the Power Outage Monitor.  On power up a flashing character 

showing S-

C will show next to the time as a reminder that the clock needs to be reset.  

Each time the Herpstat 

is powered on it increments the Power Outage Monitor.  To reset the monitor to zero press the + button. 

 

 

 

This display indicates the current time schedule the output is adhering to.  

If the NiteCycle is disabled on the 

output it wi

ll always show Day Cycle.  If the

 output's mode is set to disabled then it will also show disabled here. 

 

 

 

 

 

 

Summary of Contents for Herpstat HP

Page 1: ...re efficiency High Low threshold alarms Settings are retained in memory even if power is lost Power Outage detection tracking Temperature can be set displayed in Fahrenheit or Celsius Easy to read backlit LCD display 12ft removable sensor allows for easy replacement if necessary Audible alarm system Internal error detection shuts off heat if sensor fails or is disconnected Handles up to 1500 watts...

Page 2: ...select options while the Plus and Minus buttons are used to alter the options or navigate the menu If no selection is made after a period of time the unit will return to operation automatically While in the menu system all AC power to the outputs are turned off for safety Note Adjust the Time to insure proper operation Press the Enter button to display the initial menu screen This screen allows yo...

Page 3: ... the included temperature sensor for heating cooling modes and the optional humidity sensor for the RH mode Heat mode is for standard thermostat heating operation The Cooling mode applies power when the set temperature is exceeded The Cooling mode then powers off the output when the temp drops below the Swing setting Daytime Temperature The Daytime Temperature setting is the temperature the device...

Page 4: ... PLUS button on the main display that shows the probe temperatures This will allow another 30 minutes before the Low Alarm becomes active again Sensor Adjustment The Sensor Adjustment setting is used to alter the temperature read by the temperature probe to match other equipment Note The sensor used in the Herpstat Probes are typically more accurate than most other equipment Adjustments to this se...

Page 5: ...hieve is in parentheses When ramping is enabled for temperature the value in parentheses will change according to the time based curve Special Symbols Next to the number of the output an arrow symbol will appear if that output is currently in a ramping session A right arrow will appear if the ramp is increasing A left arrow will appear if the ramp is decreasing Next to the number of the output a m...

Page 6: ...ices Preferably leave at least a few inches between the probe wires and the AC lines to avoid cross talk electrical interference issues Getting Help Questions or comments can be e mailed to support herpstat com To purchase accessories please visit us on the web at http www spyderrobotics com 1 Year Limited Warranty Spyder Robotics LLC warrants this product to be free from defects in workmanship an...