SPX SGS REFRIGERATION STC Series User Manual Download Page 3

 3

receiving and installation

1 RECEIPT OF EQUIPMENT

1.1 INSPECTION 

All equipment should be carefully checked for damage or shortages 
as soon as it is received. Each shipment should be carefully 
checked against the bill of lading. If any damage or shortage is 
evident, a notation must be made on the delivery receipt before 
it is signed and a claim should then be filed against the freight 
carrier. Inspection and claims are the responsibility of the recipient.. 

1.2 LOSS OF GAS HOLDING CHARGE 

Each copper, steel, and stainless steel tube STC unit is leak 
tested, evacuated to remove moisture and then shipped with a 
gas holding charge. Absence of this charge may indicate a leak 
has developed in transit. The system should not be charged with 
refrigerant until it is verified that there is no leak, or the source of 
the leak is located. If the unit contains aluminum tubes or flanged 
refrigerant connections, the unit is leak tested and evacuated but 
a gas holding charge is not provided. 

2 ASSEMBLY OF COMPONENTS 

2.1 SHIPPED LOOSE PARTS 

Dielectric Flange Union with required bolts, nuts, and gaskets 
(if the coil contains aluminum tubes); TEV supply shipped loose. 

2.2 DIELECTRIC FLANGE UNION 

Aluminum tube evaporators have aluminum flanged refrigerant 
connections. A dielectric flange union to attach steel pipe to the 
aluminum evaporator flange is provided in a separate box. The box 
should contain dielectric bolt gaskets, bolts, nuts, flange gasket, 
and mating steel socket weld flange. To avoid material damage 
during assembly, preweld a length of refrigerant pipe to the steel 
flange before assembly to the aluminum flange. See Section 6.2 
for the aluminum to steel flange assembly drawing .

2.3 REFRIGERANT DISTRIBUTOR NOZZLE 

For a direct expansion system, the STC Series units already have 
the distributor nozzle installed. As a check, see that the nozzle is 
in the distributor, or the auxiliary hot gas tee for direct expansion 
halocarbon with hot gas defrosts, before installing the thermal 
expansion valve to the distributor or auxiliary hot gas tee.

2.4 EXPANSION VALVE 

(Optional Item)

 

Before hanging a unit with a direct expansion design, install the 
expansion valve and connect the equalizer tube. The expansion 
valve should be installed directly to the distributor body or as close 
as possible with no elbows or bends. Steel expansion valves for 
ammonia requires the removal of the discharge tube. Locate the 
expansion valve bulb on a horizontal length of suction line closer 
to the connection stub. Position the bulb in a 3, 4, 8, or 9 o’clock 

position. Do not position the bulb on the top or the bottom of the 
pipe. Clamp the bulb down flush and tight against the pipe and 
insulate. Never locate the bulb on a trap or downstream from a trap. 
Expansion valves are NOT adjusted at the factory prior to shipment. 
It is important that the operation of the expansion valve be checked 
after the system has balanced out at the desired room temperature. 
If the coil is being starved it is necessary to reduce the superheat 
setting of the valve by turning the adjusting stem counter-clockwise. 
If the superheat is too low it is necessary to increase the superheat 
setting of the valve by turning the adjusting stem clockwise. It is 
recommended that for a 10°F to 12°F T.D. system, the valve be 
adjusted to maintain 5°F to 6°F of superheat.

3 RIGGING INSTRUCTIONS 

An STC unit tends to be a long and heavy object with two coils. 
Jobsite requirements will affect the method of moving and lifting 
the unit into place. Carefully consider the support that is required 
to lift and move the unit. To ensure that the unit is not bowed 
or damaged when being lifted into place from above, all leg or 
hanger points should be used. If the unit is being lifted into place 
from underneath, a level support directly under all of the shipping 
legs is required to adequately steady the unit as it is lifted to the 
hanger rods.. 

4 UNIT LOCATION AND MOUNTING
 
4.1 UNIT LOCATION 

Unit must be located to provide good air circulation to all areas. 
Space around the unit should allow for free airflow into and out 
of the unit. Light fixtures, shelving, ceiling structures, and product 
boxes must be located so that they do not block the air discharge 
from the unit.
On all units a space should be provided for the possible future 
replacement of the electric defrost heaters if heaters have been 
furnished. Table 1 specifies the recommended access dimensions 
that are needed to remove the heater rods on one or both ends 
of the unit. 

4.2 MOUNTING 

The STC units are ceiling hung or floor mounted (12” legs). Ceiling 
hung units should be suspended with 1/2” diameter threaded 
STEEL hanger rods. Do not use nylon-threaded rods. Rods should 
have double nuts on the top and bottom. Adequate support must 
be provided to hold the weight of the unit. Refer to the unit drawing 
supplied with the unit or the catalog for the approximate unit weight 
and hanger locations. All hanger holes on the coil support angle 
should be used to support the unit. Do not temporarily support a 

Summary of Contents for SGS REFRIGERATION STC Series

Page 1: ...STC Series twin unit cooler INSTALLATION OPERATION MAINTENANCE E329630 ISSUED 02 2020 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual SGS REFRIGERATION...

Page 2: ...Interpiping 8 6 4 Evacuation and Leak Test 8 6 5 DXA And Suction Accumulators 8 7 Electrical 9 7 1Field Wiring 9 7 2Electrical Data 9 7 3Suggested No Defrost Requirement Sequence of Operation 17 7 4S...

Page 3: ...ocate the expansion valve bulb on a horizontal length of suction line closer to the connection stub Position the bulb in a 3 4 8 or 9 o clock position Do not position the bulb on the top or the bottom...

Page 4: ...ould be in place before the unit is hung See Sections 2 3 and 2 4 The unit must be level in all directions to insure proper drainage of the condensate drain pan FIGURE 1 Unit Dimension 15 75 5 25 LENG...

Page 5: ...00 64 00 24 00 94 00 59 75 8 115 00 70 00 24 00 94 00 65 75 30 4 133 00 62 00 28 00 112 00 57 75 68 68 6 133 00 70 00 28 00 112 00 65 75 8 133 00 76 00 28 00 112 00 71 75 Four 24 4 145 00 56 00 24 00...

Page 6: ...m moist air from migrating through the drain line The trap should be located in the warmest and or lowest section of the piping to avoid freezing and provide sufficient liquid head for flow through th...

Page 7: ...gnized refrigeration standards Under no circumstances should the refrigerant connection size of the unit be used as the basis for sizing the lines For aluminum flange connections see Figure 4 for fina...

Page 8: ...4 EVACUATION AND LEAK TEST Whenallrefrigerationconnectionshavebeencompleted theentire system must be tested for leaks and then evacuated 6 5 DXA AND SUCTION ACCUMULATORS DonotuseunitswithDirectExpans...

Page 9: ...3 5 2 5 Two 1140 1 3 3 6 1 8 1 8 1140 1 2 4 8 2 4 2 4 2 0 850 1 2 5 2 2 6 2 6 2 6 1140 3 4 5 6 2 8 2 8 2 4 850 3 4 8 0 4 0 4 0 3 2 1140 1 7 2 3 6 3 6 3 0 850 1 8 4 4 2 4 2 3 6 1140 1 1 2 10 0 5 0 5 0...

Page 10: ...0 575 3 60 1 2 3 G 1 2 3 G 1 2 3 G 1 2 3 G 1 2 3 G 1 T2 T1 T3 2 3 G GRN FAN MOTORS 3 PHASE FAN MOTOR CIRCUIT TERMINAL BLOCK INSIDE UNIT 1 3 G 1 3 G 1 3 G 1 3 G 1 3 G 1 T2 T1 T3 3 G GRN FAN MOTORS SING...

Page 11: ...HEATER CIRCUIT 2 HEATER CIRCUIT 3 HEATER CIRCUIT 4 2 B 1 R 4 Y 1 R 2 B 4 Y ADJUSTABLE DEFROST CONTROL MOUNTED ON BEND END OF UNIT ELECTRICAL ENCLOSURE BEND END OF UNIT JUMPER BLOCK INSIDE UNIT 4 PLAC...

Page 12: ...CONTROL CIRCUIT HEATER CIRCUIT 1 HEATER CIRCUIT 2 HEATER CIRCUIT 3 HEATER CIRCUIT 4 2 B 1 R 4 Y 1 R 2 B 4 Y ADJUSTABLE DEFROST CONTROL MOUNTED ON BEND END OF UNIT ELECTRICAL ENCLOSURE BEND END OF UNIT...

Page 13: ...2 58 27 35 27 35 42 58 34 06 STC4 43 A STC4 44 A 4 20 00 28 26 28 26 31 91 26 36 21 09 STC4 63 A STC4 64 A 4 28 00 35 79 35 79 43 32 35 79 28 63 STC4 83 A STC4 84 A 4 36 00 47 08 47 18 29 66 29 66 47...

Page 14: ...C 3 32 60 42 00 43 83 26 78 26 78 42 00 33 60 STC3 46 C 3 25 40 32 49 32 49 39 33 32 49 25 99 STC3 66 C 3 39 80 31 45 17 61 31 45 17 61 32 25 32 25 26 64 26 64 40 83 STC3 86 C 3 47 00 39 72 21 65 39...

Page 15: ...25 13 80 STC3 66 A 3 18 00 45 18 27 35 22 59 18 07 STC3 86 A 3 24 00 33 89 33 89 41 02 33 89 27 11 STC4 43 A STC4 44 A 4 16 00 41 48 27 35 22 59 18 07 STC4 63 A STC4 64 A 4 16 00 41 48 27 35 22 59 18...

Page 16: ...0 27 11 27 11 32 82 27 11 21 69 STC3 83 C STC3 84 C 3 28 80 38 43 38 43 46 52 38 43 30 74 STC3 46 C 3 21 60 27 11 27 11 32 82 27 11 21 69 STC3 66 C 3 28 80 38 43 38 43 46 52 38 43 30 74 STC3 86 C 3 36...

Page 17: ...H The defrost timer energizes the liquid line solenoid valve allowing refrigerant to flow into the unit cooling the coil and refreezing any remaining condensate drops that are still present I The fan...

Page 18: ...tor is when the defrost relief valve reads 5 PSI above suction pressure For FLOODED refrigeration systems check to make sure the float valve is working properly and allows refrigerant into the drum to...

Page 19: ...e any work is performed Remove the fan guard as described in Section 9 3 Loosen two bolts from the bushing that hold the fan onto the motor shaft Remove the fan Clean and deburr the motor shaft if nec...

Page 20: ...315562 850 1 2 E315550 E315540 E315574 1 30 36 BC E315563 850 3 4 E315551 E315541 E315575 1 30 36 BD E315564 850 1 E315552 E315542 E315576 1 30 36 BE E315565 850 1 5 E315553 E315543 E315577 Table 8 Co...

Page 21: ...ntenance Date Performed Drain Pan Inspection and Cleaning Cabinet and Coil Inspection and Cleaning Motor Inspection Fan Inspection Electric Heater Inspection Water Defrost Pan Inspection 11 MAINTENANC...

Page 22: ......

Page 23: ......

Page 24: ...ERVED In the interest of technological progress all products are subject to design and or material change without notice SPX COOLING TECHNOLOGIES INC 7401 WEST 129 STREET OVERLAND PARK KS 66213 USA 91...

Reviews: