B. The condensate flows through the feed line
(1)
into
the condensate drain and accumulates in the housing
(2)
. A capacitive sensor
(3)
continuously registers the
liquid level. As soon as the container is filled, a fixed
waiting period begins during which more condensate
accumulates. After the waiting time has expired the
pilot valve (4) is then activated and the diaphragm
(5)
opens the outlet line
(6)
for discharging the
condensate.
When the condensate drain has been emptied, the
outlet line is closed again quickly and tightly without
wasting compressed air.
NOTE: If there is no power to the control board for
a period of two weeks or more, it may return to the
default mode.
C.
Program Monitor
Press and hold Program Mode button until Main Menu screen
appears. Use the Up and Down arrow buttons to scroll
through the list of submenu choices. Press Enter button
to view the submenu that is displayed. Press ESC to exit the
Main Menu and return to Display mode.
1. Language selection
a. Use the ‘Up’ and ‘Down’ arrow buttons to scroll
through the list of languages (choice of 13 available:
English, Spanish, French, German, Portuguese, Italian,
Polish, Danish, Dutch, Norwegian, Finnish, Swedish
and Czech).
b. Press ‘Enter’ button to select the language that is
displayed.
c. Push ‘ESC’ at any time to return to the Main Menu.
2. Setting Date & Time
a. Press ‘Enter’ to edit value.
b. Use the ‘Up’ and ‘Down’ arrow buttons to set year
(00 to 99 representing 2000 to 2099). Press ‘Enter’
to accept new value.
c. Use the ‘Up’ and ‘Down’ arrow buttons to set month
(1-12). Press ‘Enter’ to accept new value.
d. Use the ‘Up’ and ‘Down’ arrow buttons to set day
(01 to maximum for the month and year selected).
Press ‘Enter’ to accept new value.
e. Use the ‘Up’ and ‘Down’ arrow buttons to set hours
(00 to 23). Press ‘Enter’ to accept new value.
f. Use the ‘Up’ and ‘Down’ arrow buttons to set minutes
(00 to 59). Press ‘Enter’ to accept new value.
g. Press ‘Enter’ to accept new value. Push ‘ESC’ at any
time to return to the Main Menu.
3. Setting Schedule
a. Use the ‘Up’ and ‘Down’ arrow buttons to select
desired “Day of week + on/off”. Press ‘Enter’ to
adjust time.
b. Use the ‘Up’ and ‘Down’ arrow buttons to set hour
(00 to 23). Press ‘Enter’ to accept new value
NOTE: If the hour setting is ‘--:--’, Press ‘Enter’ again
to move the cursor under the “Day of week + on/
off”.
c. Use the Up and Down arrow buttons to set minutes
(00, 10, 20, 30, 40, 50; not shown if hour setting is
‘--:--’). Press ‘Enter’ to accept new value and return
to “Day of week + on/off”. Repeat steps a through
c as needed.
d. Push ‘ESC’ at any time to return to the Main Menu.
4. Hours To Service
a. Use the ‘Up’ and ‘Down’ arrow buttons to scroll
through the range of permissible values (0 to 9999)
before service reminder is initiated. Press ‘Enter’
to move to next field. (Only hours that refrigeration
compressor is operating are counted).
2.0 OPERATION
2.1 Minimum/Maximum Operating Conditions
A.
Maximum inlet air pressure: refer to dryer serial number
tag
B. Minimum inlet air pressure: 30 psig (2.1 kgf/cm
2
)
C. Maximum inlet air temperature: 120°F (49°C)
D.
Maximum ambient temperature:
Air-cooled models: 110°F (43°C)
Water-cooled models: 130°F (54°C)
E. Minimum ambient temperature: 40°F (4.4°C)
2.2 Start-up
A.
Models 0.5 & 0.75:
Energize compressor by positioning the on/off switch in
the on (I) position. Compressor on light will illuminate.
On/Off
Power-On
Dewpoint Indicator
Switch
Light
(Green)
B.
Models 1.0 - 3.5:
Energize dryer. Green power on light will illuminate.
IMPORTANT: Energize dryer disconnect switch (provided
by others, see NEC) 24 hours before refrigeration
compressor is started! Never use the disconnect switch
to shutdown the dryer for a extended period of time
(except for repair). Failure to follow these instructions
may result in a non-warrantable compressor failure.