background image

—  50 —

  Models 40 through 3000 are equipped with a single safety relief 

valve that has been sized at a minimum to provide overpressure 

protection due to a fire for both desiccant towers.

9.2.8.2  Valves – Models 4100 through 5400

  Inlet switching valves are resilient seated butterfly valves with 

double acting pneumatic rack and pinion actuators.  A yellow arrow 

indicator located on the top of the actuator output shaft points 

to valve position indicator icons. Pilot air is directed to actuator 

ports to open both inlet valves upon loss of power.

  Purge/repressurization valves are resilient seated butterfly valves 

with spring return, fail closed, pneumatic rack and pinion actuators.  

A yellow arrow indicator located on the top of the actuator output 

shaft points to valve position indicator icons. Pilot air is directed to 

actuator ports to close both purge/repressurization valves upon 

loss of power.

  12 volt DC, single solenoid, 4-way pilot valves are wired to the 

controller and are used to direct pilot air to the actuators of the 

inlet switching and purge/repressurization valves.

  Two mainline outlet and two smaller purge line check valves are 

installed in the upper piping to control the flow of outlet and purge 

air.  Check valve sticking will result in excessive air discharge 

through a muffler. Excessive air discharge through the muffler 

can be associated with a leaking outlet check valve on the same 

side or a purge check valve of the opposite side tower.

  Purge pressure and subsequent flow is adjusted by means of 

a throttling globe valve located in the bypass line of the upper 

piping 

  Models 4100 through 5400 are equipped with multiple safety relief 

valves that have been sized to provide overpressure protection 

for capacities equal to or greater than the adjusted capacity of 

the dryer at its maximum operating pressure.

  The tower pressure gauge of the online tower should read line 

pressure. Air should not be leaking from the purge-repressurization 

valve of the on-line tower.

  The tower pressure gauge of the offline tower should read below 

2 psig (0.14 barg) while that tower is purging. If excessive air is 

exhausting during the purge cycle, the inlet-switching valve on 

the same side may have failed to close or a check valve may be 

sticking.

9.3  Operating Sequence

9.3.1  Operating sequence – Timer Based Controllers

The operating sequence for dryers equipped with Timer Based 

Controllers appears in Tables 6.1 and 6.2.
9.3.2  Operating sequence – Level 1 Controllers

The operating sequence for dryers equipped with Level 1 Controllers 

appears in Tables 7.3 and 7.4.
9.3.3  Operating sequence – Level 2 Controllers

The operating sequence for dryers equipped with Level 2 Controllers 

appears in Tables 8-2, 8-3, and 8-4.

9.4  Dryer Shut Down

  If the dryer installation is equipped with dryer bypass and inlet 

and outlet isolation valves, the bypass valve should be opened 

and the inlet and outlet isolation valves closed.

  De-pressurize the dryer by allowing the controller to run through 

tower change cycles until pressure gauges on both towers read 

zero. Manual test mode may be used to speed up this process. 

NOTE: Below 60 psig (4.1 barg) purge/repressurization valves 

may not open. Opening the manual drain on the pilot air filter 

or any mounted pre or afterfilters may bleed off remaining 

pressure.

 Turn dryer off using on-off switch (indicating LEDs 

extinguished).

9.5  Loss of Power

Control valves are designed so that upon loss of power the air dryer 

is capable of drying air until the desiccant exposed to the airflow is 

saturated.

9.6  Operating Parameters

Verify that dryer is operating within the following design parameters:
9.6.1  Maximum Operating Pressure (MOP): 

  150 psig (10.3 barg) is standard.

  250 psig (17.2 barg) is optional.

Refer to Dryer Serial Number Tag.
WARNING - Do not operate the dryer at pressures above the 

maximum operating pressure shown on the serial number tag.
NOTE: Consult factory for applications requiring higher maximum 

operating pressures.
9.6.2  Minimum Operating Pressures:
9.6.2.1  For 150 psig (10.3 barg) MOP models -

  60 psig (4.1 barg) is the minimum operating pressure for dryers 

operated on a 4,10,16, or 24-minute cycle.

9.6.2.2  For 250 psig (17.2 barg) MOP models -

  120 psig (8.3 barg) is the minimum operating pressure for dryers 

operated on a 4,10,16, or 24-minute cycle.

Refer to Dryer Serial Number Tag.
WARNING - Do not operate the dryer at pressures below the minimum 

operating pressure shown on the serial number tag.
NOTE: Consult factory for applications requiring lower minimum 

operating pressures.
9.6.3  Maximum Compressed Air Temperature at Dryer Inlet: 

  140°F (60°C) for all models.

9.6.4  Ambient Temperatures:
9.6.4.1  Minimum Ambient Temperature:

  Standard units: 35°F (2°C)

  Units with optional low ambient package: -20°F ( -29°C)

9.6.4.2  Maximum Ambient Temperature: 

  120°F (49°C)

NOTE: If dryer is installed in ambients below 35°F (2°C), low ambient 

protection requiring heat tracing and insulation of the prefilter bowls, 

auto drains and/or sumps, and lower piping with inlet switching and 

purge/repressurization valves is necessary to prevent condensate 

Summary of Contents for Hankinson HHE Series

Page 1: ...HHS 60 HHS 90 40 SCFM 60 SCFM 90 SCFM 40 60 90 HHE 115 HHE 165 HHE 260 HHL 115 HHL 165 HHL 260 HHS 115 HHS 165 HHS 260 115 SCFM 165 SCFM 260 SCFM 115 165 260 HHE 370 HHE 450 HHE 590 HHL 370 HHL 450 HH...

Page 2: ...VING UNPACKING 1 3 DESCRIPTION 2 4 INSTALLATION 7 5 CONTROLLERS GENERAL 15 6 CONTROLLER TIMER BASED 17 7 CONTROLLER LEVEL 1 20 8 CONTROLLER LEVEL 2 31 9 OPERATION 48 10 MAINTENANCE 54 11 TROUBLESHOOTI...

Page 3: ...aims are not our responsibility as our terms are F O B point of shipment 1 GENERAL SAFETY INFORMATION 1 1 Pressurized Devices This equipment is a pressure containing device Do not exceed maximum opera...

Page 4: ...heat of adsorption and is stored in the bed for use during regeneration Desiccant is regenerated by driving off desorbing the water collected on its surface Pressure swing also called heatless or heat...

Page 5: ...o repressurize slowly Adequate repressurization time is allowed so that tower 4B is fully repressurized before tower switchover After a controlled time period purge and repressurization valve 9A norma...

Page 6: ...uate repressurization time is allowed so that tower 4B is fully re pressurized before switchover After a controlled time period air inlet switching valve 3B normally open opens and inlet switching val...

Page 7: ...repressurization time is allowed so that tower 4B is fully re pressurized before switchover After a controlled time period air inlet switching valve 3B normally open opens and inlet switching valve 3...

Page 8: ...emperature rise to occur depends on flow rate At 100 flow the temperature rise takes 5 minutes at 50 flow it takes 10 minutes NOTE If after 30 minutes the bed temperature has not risen to the calculat...

Page 9: ...ovide a reservoir of stored air for response to system demands in excess of compressor capacity Size and location of receivers in the compressed air system need to be considered carefully Flows must n...

Page 10: ...UGE MOISTURE INDICATOR RIGHT CHAMBER PRESSURE GAUGE CONTROL ENCLOSURE DESICCANT DRAIN PORT G H P AIR OUTLET 7 8 X 1 1 4 SLOT TYP 4 PLCS 22mm 32mm A L MAX F N MAX P AIR INLET TOP VIEW FRONT VIEW RIGHT...

Page 11: ...58 M 35 35 35 41 41 41 42 42 N 49 64 81 57 57 75 65 73 P 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 2 NPT 2 NPT 2 NPT WT LBS 365 445 575 685 685 1010 1215 1350 DIMENSIONS IN MILLIMETERS MODEL 40 60 90 115 165 260...

Page 12: ...ROL ENCLOSURE RIGHT CHAMBER PRESSURE GAUGE PURGE PRESSURE GAUGE MOISTURE INDICATOR DESICCANT FILL PORT 7 8 X 1 1 4 SLOT TYP 4 PLACES 22mm 32mm A B LEFT CHAMBER PRESSURE GAUGE LIFTING LUG PURGE PRESSUR...

Page 13: ...59 59 59 67 N 104 107 112 115 120 117 119 125 P 2 NPT 2 NPT 2 NPT 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE WT LBS 1473 2134 2414 2875 3722 4167 4417 9010 DIMENSIONS IN MILLIMETERS MODEL 590 750 93...

Page 14: ...INE OF CUSTOMER INLET OUTLET CONNECTIONS LIFTING LUG PURGE PRESSURE ADJUSTMENT VALVE LEFT CHAMBER PRESSURE GAUGE DESICCANT FILL PORT MOISTURE INDICATOR PURGE PRESSURE GAUGE RIGHT CHAMBER PRESSURE GAUG...

Page 15: ...9 7 16 H 115 13 16 116 3 16 J 36 3 16 38 7 8 L 100 105 M 88 89 N 124 124 P 6 FLANGE 6 FLANGE WT LBS 9900 12000 DIMENSIONS IN MILLIMETERS MODEL 4100 5400 A 2106 2372 B 1053 1186 C 32 32 D 1511 1613 E 7...

Page 16: ...d outlet piping as indicated NOTE All piping must be supported so as not to bear on the dryers or filters 4 10 Isolation Valves If isolation or bypass valves are installed care must be used to ensure...

Page 17: ...age Desiccant Dryer Controllers Timer Controller Level 1 Fixed Cycle Only Level 2 Fixed Cycle and APSS Category Feature General AC Input Voltage 100 240 VAC 50 60 Hz See NOTE 1 AC Input Voltage 85 264...

Page 18: ...ower is restored after an interruption 4 Level 1 Level 2 Controllers The service reminder LEDs indicate that it is time to perform preventive maintenance on the a filters and drains b valves or c desi...

Page 19: ...rent AC input power connection of 100 240VAC 1 ph 50 60 Hz can be made at terminals mounted within the control enclosure See reference figures for proper polarity Program Step 1 2 3 4 5 6 7 8 Left tow...

Page 20: ...nel Overlay Timer Based Controller NOTE Figure is representative of Models 40 through 3000 WARNING Disconnect the main power supply before removing this cover Power ON Light Left Tower DRYING Light Ri...

Page 21: ...E BLACK Live Neutral Earth 100 240v 50 60 Hz FUSE 5 x 20mm 1 Amp Slow Blow FUSE 5 x 20mm 1 Amp Slow Blow VOLTAGE LABEL SUPPLY INPUT TERMINALS 100 240V 50 60 Hz TOP CONTROL TIMER BOARD BASE EARTH POSIT...

Page 22: ...ls and there are no alarms The coil is de energized when power is removed or when an alarm condition exists The common alarm is designed to activate on a either a dryer fault condition or a service re...

Page 23: ...filter LEDs amber 7 3 3 2 Desiccant Service When the service interval for desiccant has expired the following LEDs will blink Service LED amber Both tower regenerating LEDs amber The service function...

Page 24: ...purge valve LED On valve open Off valve closed Left tower regenerating LED Filter service maintenance LED Operating mode LEDs ISO Class 1 4 Operating mode selector switch Power On LED Power On Off Swi...

Page 25: ...pproximately 2 seconds The current ISO Class LED will remain illuminated and the Manual cycle mode LED will illuminate When in the Manual cycle mode the dyer can be advanced one step at a time using t...

Page 26: ...3 13 05 33 08 41 00 40 02 25 04 33 07 29 10 01 05 03 37 06 14 09 46 00 44 02 43 05 07 08 25 0 01 12 04 00 06 55 10 50 00 48 03 00 05 40 09 20 t4 all 02 00 05 00 08 00 12 00 02 00 05 00 08 00 12 00 t5...

Page 27: ...w tower pressured open1 open1 Right tower regenerating Fail to de pressurizee closed1 Right tower regenerating Fail to re pressurizef open2 NOTE Stop cycle on fault Comments 1 Check for fault conditio...

Page 28: ...6 43 44 41 G Y Y G Y G Y SERVICE REMINDER 1 PILOT AIR FILTER PRESSURE SW 2 RIGHT TOWER CLOSED SERVICE REMINDER 2 AFTER FILTERS RIGHT TOWER DRYING ENERGY SAVINGS 70 MAIN SERVICE REMINDER COMMON ALARM P...

Page 29: ...Z PE NEU HOT JUMPER JUMPER PINS JUMPER BASE JUMPER OFF JUMPER ON ENCLOSURE INTERIOR AC TO DC POWER SUPPLY RED WIRE TO TB4 18 BLK WIRE TO TB4 19 CONTROL BOARD TB1 TB2 TB3 TB4 TB5 1 2 3 4 5 6 7 8 9 10 1...

Page 30: ...11L RIGHT PURGE VALVE OPEN GREEN 12L RIGHT TWR DRYING GREEN 13L POWER ON LED GREEN 14L MAIN SERVICE REMINDER AMBER 15L COMMON ALARM RED 16L PRESS SWITCH 2 R TWR CLOSED GREEN 17L ENERGY SAVINGS LEDS G...

Page 31: ...29 Figure 7 4 Panel Layouts Level 1 Controller continued from previous page 47 63 HZ 85 264 VAC 11 5 28 VDC...

Page 32: ...18 0 181 4 6 0 312 7 9 PG 9 0 599 15 2 3 SOLENOID LEFT PURGE VALVE 2 18 0 181 4 6 0 312 7 9 PG 9 0 599 15 2 4 SOLENOID LEFT INLET VALVE 2 18 0 181 4 6 0 312 7 9 PG 9 0 599 15 2 5 SOLENOID RIGHT PURGE...

Page 33: ...ists The common alarm is designed to activate on a either a dryer fault condition or a service reminder or b a dryer fault condition only This is user selectable For the common alarm to activate on ei...

Page 34: ...Jumper JP6 Common Alarm Jumper JP6 is installed in the OFF position to enable both dryer fault alarms and service alarms to activate the common alarm This is the default configuration Install jumper...

Page 35: ...D On switch closed Off switch open Left tower drying LED Left purge valve LED On valve open Off valve closed Left tower regenerating LED Filter service maintenance LED Vacuum Fluorescent Text Display...

Page 36: ...i 2000 hours for filters ii 4000 hours for desiccant iii 2000 hours for valves NOTE Time continues to accumulate as long as power is supplied to the controller whether the controller is switched on or...

Page 37: ...s a brief description of each alarm 1 Left or right tower drying low pressure Pressure switch open during drying cycle 2 Left or right tower regenerating high pressure Pressure switch closed while pur...

Page 38: ...ER SENSOR UNDER RANGE 8 9 1 10 Alarm Mode Screen 7 Left Tower Lower Sensor Thermistor Over Range ALARM LEFT TOWER LOWER SENSOR OVER RANGE 8 9 1 11 Alarm Mode Screen 8 Right Tower Drying Low Pressure O...

Page 39: ...rly Inspect pilot air filter element Check filter monitors if equipped 8 9 2 2 Service Mode Screen 2 Service desiccant SERVICE DRYER DESICCANT Check moisture indicator or outlet dew point and inspect...

Page 40: ...right that corresponds to the temperature display Press to advance to screen 4 8 11 4 Test Mode Screen 4 Step 4 TEST MODE STEP 4 XX C XXX F The left tower drying light is blinking to indicate the ther...

Page 41: ...oid see NOTE 1 off on on on off off off off Right purge solenoid off off on off off off off off Inlet shuttle valve see NOTE 2 open to left chamber open to right chamber Left inlet valve see NOTE 1 op...

Page 42: ...08 00 12 00 t5 02 02 05 02 08 02 12 02 02 02 05 02 08 02 12 02 t6 02 06 05 06 08 06 12 06 02 06 05 06 08 06 12 06 t7 03 12 09 00 14 55 22 50 02 48 08 00 13 40 21 20 t8 04 00 10 00 16 00 24 00 04 00 1...

Page 43: ...ult Comments 1 Check for fault condition at 15 25 35 seconds into the half cycle no If the fault condition is clear for 1 cycle the alarm LED stays on without blinking and the alarm message continues...

Page 44: ...137 142 145 143 144 141 140 139 138 132 136 135 134 133 131 130 129 128 126 125 124 123 121 122 120 119 118 116 117 115 114 113 110 111 112 109 108 107 J1 1 J1 34 5 J1 4 J1 2 J1 33 J1 13 SERVICE MAIN...

Page 45: ...oint to Point Diagram Level 2 Controller continued on next page 3 2 1 5 4 8 7 6 J2 RPB ENCLOSURE DOOR ENCLOSURE DOOR INTERIOR REMOTE PUSHBUTTON SWITCH CONNECTIONS 1 7 8 6 5 4 3 2 ALARM_RESET POWER ON...

Page 46: ...D JP7 NOT USED 150 PSIG 250 PSIG NO YES DEFAULT 1 2 9 8 7 6 5 4 3 19 18 17 16 15 14 13 12 11 10 20 21 22 23 24 25 26 27 28 29 35 39 38 37 36 34 33 32 31 30 40 41 TB4 TB3 TB2 TB1 NOTES 1 SEE FIGURE 8 5...

Page 47: ...R 1 PILOT AIR FILTER AMBER 8L SERVICE REMINDER 2 AFTER FILTERS AMBER 10L RIGHT TOWER REGENERATING AMBER 11L RIGHT PURGE VALVE OPEN GREEN 12L RIGHT TOWER DRYING GREEN 13L POWER ON INDICATOR GREEN 14L M...

Page 48: ...C8 C7 C6 U1 C28 Y1 U5 J4 C21 J5 R21 L4 L5 F1 C11 R15 C22 L3 R16 1 R52 L2 C10 C5 J3 J1 J2 C13 JP8 JP7 JP6 JP5 JP4 JP3 JP2 JP1 R10 R9 R8 R7 R6 R5 R4 R3 R2 R1 C14 C1 U3 U4 C15 R14 C18 C20 U8 C39 C33 C29...

Page 49: ...9 0 250 6 4 PG 7 0 492 12 5 4 THERMISTOR 2 RIGHT TOWER UPPER 2 22 0 114 2 9 0 250 6 4 PG 7 0 492 12 5 5 THERMISTOR 3 LEFT TOWER LOWER 2 22 0 114 2 9 0 250 6 4 PG 7 0 492 12 5 6 THERMISTOR 4 RIGHT TOW...

Page 50: ...he required pressure The purge pressure adjustment valve on Models 40 through 3000 is a quarter turn ball valve located in the smaller bypass line of the upper piping of the dryer Refer to Figures 4 2...

Page 51: ...either tower fails to pressurize or de pressurize to the required levels at the proper time Refer to Section 7 4 3 and Table 7 4 NOTE Alarm will activate if dryer is energized without being pressurize...

Page 52: ...rating sequence Level 1 Controllers The operating sequence for dryers equipped with Level 1 Controllers appears in Tables 7 3 and 7 4 9 3 3 Operating sequence Level 2 Controllers The operating sequenc...

Page 53: ...purge repressurization cycle It includes the maximum purge flow for a portion of the purge repressurization time and the volume of air used for repressurization averaged over the cycle time For avera...

Page 54: ...3 2 2 2 1 2 1 2 1 2 0 1 9 ISO CL 3 16 min psig 18 17 16 15 14 13 35 33 32 30 29 28 27 26 25 25 24 23 23 22 barg 1 2 1 2 1 1 1 0 1 0 0 9 2 4 2 3 2 2 2 1 2 0 1 9 1 9 1 8 1 8 1 7 1 7 1 6 1 6 1 5 ISO CL 4...

Page 55: ...134 0 134 0 134 10 0 135 0 133 0 131 0 129 0 128 0 127 0 126 0 126 0 125 0 125 0 125 0 125 0 125 0 125 20 0 122 0 120 0 119 0 118 0 117 0 116 0 116 0 116 0 115 0 115 0 115 0 116 0 116 0 116 30 0 110...

Page 56: ...ow rate of less than 50 of maximum rated inlet capacity until the desiccant has regenerated fully 10 2 Purge Mufflers Purge mufflers should be checked regularly changed annually Muffler disseminator e...

Page 57: ...ycle Verify removal of voltage to pilot solenoid valve Verify proper actuator operation This is a spring assisted normally closed valve Check valve for obstruction or seat damage Insufficient purge fl...

Page 58: ...RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW 7 16 2 9 10 14 8 1 3 5 6 12 10 4 13 11 13 15 16 AIR IN LEFT TOWER RIGHT TOWER AIR OUT Models 40 through 450 Phone 1 724 745 1555 FAX 1 724 745 6040 Email ha...

Page 59: ...6223 1 1 4 Outlet Shuttle Valve 3206222 3206222 3206222 3206222 3206222 3206223 3206223 3206223 1 5 Pressure Relief Valve 4010063 4010063 4010063 4010063 4010063 4010063 4010063 4010063 1 6 Adjustable...

Page 60: ...AIR IN 11 14 13 13 15 10 10 5 1 2 16 7 16 12 9 8 3 LEFT TOWER RIGHT TOWER FRONT VIEW REAR VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY Phone 1 724 745 1555 FAX 1 724 745 6040 Email hankison americ...

Page 61: ...nlet Shuttle Valve 3206223 3206223 3206223 1 4 Outlet Shuttle Valve 3206223 3206223 3206223 1 5 Pressure Relief Valve 7400684 7400684 7400684 1 6 Adjustable Purge Rate Valve 7401510 7401510 1197250 1...

Page 62: ...HT SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW 5 12 9 8 13 4 15 13 14 11 6 3 7 16 10 10 2 1 16 LEFT TOWER RIGHT TOWER AIR OUT AIR IN Phone 1 724 745 1555 FAX 1 724 745 6040 Email hankison am...

Page 63: ...163013 3163013 3163013 1 1 4 Outlet Shuttle Valve 3163014 3163014 3163013 3163013 3163013 1 5 Pressure Relief Valve 7400684 7400684 7400684 3100938 3100938 1 6 Adjustable Purge Rate Valve 1197250 1197...

Page 64: ...12 11 13 7 11 6 2 14 1A 1 2A 2B 8 FLOW FLOW FLOW FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW FLOW 8 3 4 5 LEFT TOWER RIGHT TOWER Phone 1 724 745 1555 FAX 1 724 745 6040 Email hank...

Page 65: ...4009988 1 2 5 Pressure Relief Valve 4010073 4010074 4 6 Adjustable Purge Rate Valve 7402959 7402959 1 Pilot Air Pressure Regulator 4010029 4010029 1 Purge Gauge Pressure Regulator 3204277 3204277 1 7...

Page 66: ...s _____________________________________________________________________________________________________________ Delta P devices ________________________________________________________________________...

Page 67: ...e performed on the product by anyone other than the manufacturer must first be authorized by the manufacturer Unauthorized service voids the warranty and any resulting charge or subsequent claim will...

Page 68: ...mericas spx com www hankisonintl com Improvements and research are continuous at SPX Specifications may change without notice ISSUED 03 2014 Form No 3162258 Revision H COPYRIGHT 2014 SPX Corporation H...

Reviews: