SPX Cooling Technologies Marley HP7000 User Manual Download Page 3

3

Fan Hub Installation 

The following instructions detail the process for installing a Marley 

HP7000 Fan on a Marley Geareducer

®

 with a tapered fan (output) 

shaft and bolted fan hub retention. Installation on other gear reduc-

tion units may be different. Contact your Marley sales representative 

for supplemental instructions if required.

1–Remove  the  retention  plate  and  hardware  from  the  top  of  the 

Geareducer shaft. Thoroughly clean the fan shaft, fan shaft key, 

and the fan hub center bore to remove any debris and/or protective 

coatings. After cleaning, apply a coat of anti-seize compound to the 

top 5

 (130mm) of the fan shaft.

–Prior to hub installation, fully seat the key in the fan shaft keyway. 

The key is a tight fit across the width and must never be altered.

3–Raise the fan hub above the fan shaft for installation. Slowly lower 

the hub onto the shaft with the keyways properly aligned. Make cer-

tain the key does not slide down during installation. Stake the key 

in the keyway with a center punch if necessary.
The fan shaft key should be approximately centered in the engaged 

portion of the hub when engaged on the shaft. Verify the center hub 

is fully seated by visual inspection.
4–The hub retention plate will sit on top of the spool. Discard the 

retention bolts that come with the Geareducer. New retention bolts 

are provided with the hub cover hardware kit. Torque bolts to  50 ft·lb

ƒ

 

(68 N·m).

Figure 2

Summary of Contents for Marley HP7000

Page 1: ...V i N N i iV i Marley HP7000 Fan Clamped Blade Shank 192 thru 240 User Manual 01 1139A...

Page 2: ...N NUMBER 102 131 121 122 123 133 140 132 111 200 132 100 Hub 101 Hub Center 102 Hub Plate 110 Kit Blade Clamp 111 Blade Clamp 120 Kit Center Hub Hardware 121 Cap Screw B 122 Flat Washer B 123 Pin Z x...

Page 3: ...0mm of the fan shaft 2 Prior to hub installation fully seat the key in the fan shaft keyway The key is a tight fit across the width and must never be altered 3 Raise the fan hub above the fan shaft fo...

Page 4: ...hank on a nameplate is inscribed a let ter code i e A or B etc When installing or replacing blades use only blades with the same letter code Figure 3 Blade Nameplate 1 Lubricate the C v bolt and C v h...

Page 5: ...the concave blade side TOP on the discharge side between the hub assembly plates as shown in Figure 4 Vertically align the two bolt holes in the clamps and plates Install two lubricated C v bolts four...

Page 6: ...the safety shoulder is in contact with the blade clamp then set the pitch See Figure 5 Blades should be within 1 4 of the desired pitch angle After the de sired setting is obtained progressively tigh...

Page 7: ...pect the fan for airborne debris damage contact with fan cylinder segments and corrosive attack Correct any situations determined detrimental to fan operation Remove any accumulated scale or dirt Clea...

Page 8: ...the following equation Actual volts and amperage must be obtained with the fan running and the specified rate of water flowing over the tower after the motor andGeareducerhavereachedoperatingtemperatu...