If the minimum allowable cold process fluid temperature is estab-
lished at or near minimum heat load, it should be safe for all operat-
ing conditions.

Having  established  the  minimum  allowable  cold  water  temperature, 
maintaining that temperature can be accomplished by fan manipulation, 
as outlined in 

item 4

 under 

Fluid Cooler Operation

.

 2.  A fan operating in a forced-draft tower is subject to the risk of freez-

ing. Icing is a particular danger as this can form not only on the fan 
blades, but also the inlet guard. Ice particles can be thrown off and 
cause severe damage. The fan casing should be checked so that any 
water entering it (either from the tower or external sources) can drain 
away. If water is allowed to collect in the fan casing, the fan could be 
frozen into place. This could result in damage to the drive system if 
starting were attempted.

3.   As cold air enters the fluid cooler, it causes the falling water to be 

drawn inward. Thus, under fan operation, the lower periphery of the 
fluid cooler structure remains partly dry, seeing only random splash-
ing from within the fluid cooler—plus normal atmospheric moisture 
from the entering air. Such lightly wetted areas are most subject to 
freezing.

    Although ice is unlikely to cause structural damage, it may build up 

sufficiently to restrict the free flow of air. This effectively reduce the 
fluid  cooler's  thermal  performance  efficiency.  When  excessive  ice 
forms, stop the fan for a few minutes. With the fan off, the action of the 
spray system will cause a slight downward movement of air through 
the coil and deice the fluid cooler.

intermittent Wintertime Operation:

If  periods  of  shutdown  (nights,  weekends,  etc.)  occur  during  freezing 
weather, measures must be taken to prevent the water in the cold water 
basin—and all exposed pipework—from freezing. Several methods are 
used to combat this, including automatic basin heater systems and pump 
freeze protection systems available from Marley. 

Operation

 Caution

Summary of Contents for Hexacool Air Cooled Condenser none

Page 1: ...Marley MC Fluid Cooler User Manual uk_07 1185C...

Page 2: ......

Page 3: ...n and operation of your fluid cooler Carefully read the manual before installation or operation of the fluid cooler and follow all instructions Save this manual for future reference Indicates presence...

Page 4: ...plate located on the access door Safety First The location and orientation of the fluid cooler can affect the safety of those responsible for installing operating or maintaining the fluid cooler Howev...

Page 5: ...s possible to promote ease of maintenance and to permit freedom of airflow into and through the fluid cooler If you have questions about the adequacy of the available space and the intended configurat...

Page 6: ...ure reference and maintenance purposes Hoisting Fluid Cooler All MC Fluid Cooler models consist of two modules per cell The upper module includes hoisting clips at the bottom corners Hoisting clips on...

Page 7: ...ule skid and beams and from the top of the bottom module Apply the mastic sealing strip supplied with the fluid cooler according to the MC Fluid Cooler Field Installation Drawing instructions Place to...

Page 8: ...ire motor leads as shown on the motor nameplate matching the supply voltage Do not deviate from the motor nameplate wiring Either of following symbols may be shown on the motor nameplate Y or YY These...

Page 9: ...ps Motor rotation must be the same in both VFD mode and By pass mode If cable distance between the VFD and motor is greater than 31m a DV DT output filter is recommended to avoid damage to the motor 3...

Page 10: ...jury Failure to correctly install the VFD drive will automatically void all warranties associated with the motor and any equipment that is either electrically or mechanically directly attached to the...

Page 11: ...ally and observe the action of the sheaves and belts to be sure that the motor is properly aligned with the fan sheave See Belt Tensioning and Sheave Alignment on page 21 2 Momentarily bump energize t...

Page 12: ...ntil the water reaches a level approximately 4mm below the lip of the overflow 4 Start your pump s and check for proper rotation as indicated by the arrow on the pump cover observe system operation A...

Page 13: ...r operating the fluid cooler fan After biocidal pretreatment has been successfully completed cooling water may be circulated over the tower with the fan off Whenbiocidaltreatmenthasbeenmaintainedatasa...

Page 14: ...cycled to control process fluid temperature Doing so may result in excessive and premature scaling on the coil exterior surface It is recommenced that while process fluid is being circulated through t...

Page 15: ...lies to all 7055 and 7075 MC Fluid Cooler models Multicell fluid coolers equipped with two speed motors will maximize energy savings and minimize sound levels if fans are staged so that all fans are b...

Page 16: ...luid cooler it causes the falling water to be drawn inward Thus under fan operation the lower periphery of the fluid cooler structure remains partly dry seeing only random splash ing from within the f...

Page 17: ...nt heat load on the process fluid Fluid exiting the coil must be maintained at or above 8 C Cycling of the recirculation pump should not be used to control process temperatures Draining the coil is no...

Page 18: ...0 with hardness and alkalinity levels between 100 and 300 ppm expressed as CaCO3 Chlorine if used shall be added intermittently with a free residual not to exceed 1 ppm maintained for short periods E...

Page 19: ...year The drift eliminators easily accessible surfaces and the coil should be flushed by use of a moderate pressure water nozzle being careful not to cause physical damage A reliable water treatment p...

Page 20: ...he makeup water assuming none of the solids form scale or are otherwise removed from the system When water treatment chemicals are added they should not be in troduced into the circulating water syste...

Page 21: ...tioned as close as possible to the motor in order to minimize torque on the motor bushings The motor and fan sheaves may have grooves that are not used The bottom surface of the motor and fan sheaves...

Page 22: ...of vibration Abnormal aspects relating to the rotating equipment should be considered reason to shut down the fluid cooler until the problem can be located and corrected Observe operation of the moto...

Page 23: ...he recirculation water system be drained Leave the basin drains open Draining the coil is not recommended draining promotes corro sion inside the coil tubes See protecting coil in Freezing weather on...

Page 24: ...olts and tighten as required Do not start motor before determining that there will be no interfer ence with free rotation of the fan drive The motor s should be operated for three hours at least once...

Page 25: ...shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in ad vance thus avoiding the cost of special handling Be sure to mention your flui...

Page 26: ...ion every 3 mo every 3 months every 3 months Check and tighten support fasteners x Check shaft sheave and belt alignment x Check belt tension and condition x x Check sheave bushing fastener torque x F...

Page 27: ...ments contain important information relating to safe installation and operation of the fluid cooler Field installation is required for some optional accessories A separate installation drawing or manu...

Page 28: ...nstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Wrong motor RPM Check nameplate against power supply Chec...

Page 29: ...e is above design Check to see if local heat sources are affecting fluid cooler See if surrounding structures are causing recirculation of tower discharge air Discuss remedy with Marley representative...

Page 30: ......

Page 31: ......

Page 32: ...3 8AB UNITED KINGDOM 44 0 1905 720 200 info uk spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Coolin...

Reviews: