Model 340XRi / 680XRi / 1220XRi DC drive product manual HG102909 iss 9 

 

This drive is an isolated 4 Quadrant speed controller for shunt wound or permanent magnet motors. It utilises 

speed feedback from the armature voltage (Avf), or from a shaft mounted tachogenerator. It incorporates an 

accurate current control loop to protect the drive and motor, and can be used in speed or current control 

modes. The drive can operate in forward or reverse, motoring or regenerative braking. 

Please obtain expert help if you are not qualified to install this equipment. Make safety a priority. 

This 

component is hazardous.

 

 (

All specifications in this document are nominal).

 

 

340XRi      0.55KW (0.5 HP) at 180 Volts DC, 3.4 Amps 
680XRi      0.75KW (1.0 HP) at 180 Volts DC, 6.8 Amps 
1220XRi    1.80KW (2.0 HP) at 180 Volts DC, 12.2 Amps 

Versions that work from 60V / 30V AC supply are also available. 
340XRi / LV60, 680XRi / LV60, 1220XRi / LV60.  

 

For motors rated up to 48V DC

 

 

Armature:

  +/-200 Volts DC, or +/-50V for LV60 models. 

Models 340XRi / 680XRi /1220XRi - 3.4/ 6.8/ 12.2 Amps. 

Field:

  Volts DC=  0.9 x AC supply volts.    1 Amp 

(0.45 x AC for field connected to F- and N).    1 Amp.

 

 
110V AC or 240V AC +/-10%, 50–60 Hz. 
30V AC or 60V AC +/-10%, 50-60Hz for LV60 models.

 

 

Speed range  0–100%. (motor dependant) 
Load Regulation typically 0.2% tach, 2% Arm Volts.

  

 
Presets accessible under lift up cover.  
Clockwise rotation for linear increase in parameter. 
 

Relay driver threshold 

(Level)

 

+/-(0.5% to 105%). (+/-10.5V) Symmetrical about zero. 

Maximum Speed    

(Max spd)

 

40V-200V span with Spd x 2 switch. (Avf/Tach fb volts) 

 

LV60 models have an Avf range 10 - 50V. 

Minimum  Speed    

(Min spd)

 

0 to 30% of maximum speed. (With 10K external pot). 

Up Ramp               

(Ramp   )

 

20 to 1 seconds up ramp rate.       (For 0 to +10V) 

Down Ramp           

(Ramp   )

 

20 to 1 seconds down ramp rate    (For +10 to 0V) 

Stability                     

(Stab)

 

Gain 1 to 10 

Maximum Current      

(I max)

 

0 to 100% current limit. 

IR compensation    

(IR comp)

 

0 to 25%

 

 

Speed setpoint from 

external 10K Ohms pot.

 

External RUN contact for electronic STOP/START. 

Built in functions are+/- channel with pushbutton control inputs, and relay driver with variable 
threshold. There is a pot kit available with graduated dial and knob. Sprint Electric part ref. POTKIT.

 

 
Speed loop:   Full P+I armature voltage feedback. 

 

Current loop: Full P+I isolated current feedback.

 

 

Use correctly rated cable minimum 600V AC, 1.5 times 
armature 

current. 

    

DOC# HG102909 iss 9 07/11/05

 

Sprint Electric Limited, Arundel, UK
Tel.   

+44 (0)1903 730000

Fax.   

+44 (0)1903 730893

Email. [email protected] 
www.sprint-electric.com

 

POWER RATING

 

MAXIMUM OUTPUT

 

AC SUPPLY INPUT

 

SPEED RANGE

 

USER ADJUSTMENTS

 

EXTERNAL CONTROLS

 

CONTROL ACTION

 

INSTALLATION

 