These outputs contain PTC Thermistors with a trip rating of 750 mA at 20 °C (68 °F). The PTC Thermistor current pass-
ing capacity must be de
-
rated 10 percent for each 10 °C increase in ambient temperature.
Example:
The ambient temperature where the control panel is used is 30 °C (86 °F).
The outputs will be de
-
rated by 10 percent for the 10 °C increase.
(750 mA) (.90) = 675 mA
Outputs 9 and 10:
24 VDC designated outputs, these outputs are powered directly through the circuit board.
These outputs contain PTC Thermistors with a trip rating of 200 mA at 20° C (68° F). The PTC Thermistor current pass-
ing capacity must be de
-
rated 10 percent for each 10° C increase in ambient temperature.
Example:
The ambient temperature where the control panel is used is 30° C (86° F).
The outputs will be de
-
rated by 10 percent for the 10°C increase.
(200 mA) (.90) = 180 mA
4.5 OUTPUT DETAILS
Figure 4.5: Output Connections
Terminal Block J9
O
N
E
TW
O
TH
RE
E
FO
U
R
FI
V
E
SI
X
SE
V
EN
EI
G
H
T
N
IN
E
TE
N
EL
EV
EN
TW
EL
V
E
TH
IR
TE
EN
FO
U
RT
EE
N
FI
FT
EE
N
SI
XT
EE
N
SE
V
EN
TE
EN
EI
G
H
TE
EN
N
IN
ET
EE
N
TW
EN
TY
`
+24 VDC
COM
+24 VDC
COM
Sinking Output Wiring
Sourcing Output Wiring
24 VDC
COM
Piston Pump
Solenoid
Diaphragm Pump
Solenoid
24 VDC
COM
Output 10 Wiring
Output 9 Wiring
+
+
-
-
Outputs 1 to 8 are isolated general purpose
outputs. If connecting an inductive load such as
a solenoid or relay a snubber circuit or surge
suppression circuit is required to prevent
damage to the output transistors.
Output 9 is a special output designated to
energize a solenoid coil when the system is in
“Lubrication Mode
.
”
Output 10 is a special output designated to
output a low 20
–
80 cycle per minute frequency
to a solenoid (piston pump solenoid) when the
system is in “Lubrication Mode
.
”
Output Connections
OUTPUT CONNECTIONS: TERMINAL J10