background image

12

 

SECTION 5

 

OPERATION

 

5.1 SYSTEM START

-

UP

 

ATTENTION: 

Before starting the system for the first time, be sure to follow all instructions on the drawings 

and in the 

System Hook Up

” 

Section of this manual. Always check all electrical, hydraulic, and pneumatic 

connections before powering on the system or turning on air and water supply. 

 

WARNING: The heating circuit and all fluid delivery lines should be flushed prior to connecting to 
nozzles and running the system. 

 

5.2 FILLING THE HEATING CIRCUIT

 

1.

 

Begin by turning the disconnect switch to the 

On

” 

position. 

 

2.

 

Apply power to the system using the 

Power On

” 

pushbutton. The Amber indicator will light up. 

 

3.

 

Prior to the system being run for the first time, the heating circuit must be filled with conditioning fluid. DI water is 
acceptable for temperatures of 180°F and below. For temperatures of 180°F 

-

200°F, a 50/50 mixture of propylene 

(or ethylene) glycol to DI water must be used. 

 

4.

 

Connect the conditioning fluid source to the ¼

” 

NPT (F) valve at the top of the standpipe. 

 

5.

 

To fill the reservoir, open the valve and adjust the regulator. The regulator should be set to 5psi. The over

-

pressurization valve past the regulator will open at 10psi. 

 

6.

 

Open the air purge vents on the return line and pump; these will automatically purge air out of the water line. 

 

7.

 

As conditioning fluid fills the reservoir, loosen the 1/2G level sensor connection recognizable by an O

-

ring (bottom 

connection on the stand pipe). 

 

8.

 

Allow the fluid and air mixture to escape from the loosened connection until no air bubbles are seen; hand

-

tighten 

the sensor to begin building pressure. 

 

9.

 

Once the small, yellow light on the sensor is lit, allow the system to continue to fill for several minutes. Wait until 
the inlet regulator at the top of the standpipe levels off at a pressure, making sure it is adjusted to 5psi at a no

-

flow 

condition. 

 

10.

 

Turn the pump on by using the selector switch on the system control panel. If the standpipe fluid level drops below 
the level sensor, the pump will automatically be turned off and the Pump On light will be off. 

 

11.

 

As the system continues to fill, the pump should resume operation. When the pump is running, water pressure at 
the outlet of the pump should be approximately between 20

-

35psi. 

 

12.

 

During the fill operation if the water pressure does not exceed about 20psi, make sure all the air vents are open. 
Once all air is purged out of the system, the pressure at the pump outlet should remain steady. 

 

If pressure surges on the regulator of the return reservoir, or a large amount of water is relieved out the over flow 
check valve after shutting the pump off, then air may still present in the system. 

 

13.

 

Repeat the purge process described above, and potentially try the following:

 

14.

 

Find the conditioning lines highest point and loosen the fitting until liquid is consistently leaking. 

 

15.

 

Then tighten the fitting. Loosen the point level sensor on the heated system return tube to release any air trapped. 

 

16.

 

Retighten the sensor when complete. 

 

17.

 

Excess fluid in the system will be relieved when the system is heated to your highest operating temperature.  

 

Note

: Less than 10psi could indicate air in the system, or low fluid level. 

 

WARNING:  Relieving air from the conditioning line should never be done when the system is hot; when reliev-
ing, fluid can be dispensed onto surrounding objects and people. 

 

Summary of Contents for AutoJet AccuCoat MV10

Page 1: ...1 ML00MV10HTSYS spray com AccuCoat MV10 Heated System OWNER S MANUAL...

Page 2: ...ew 5 3 1 Product Feature 5 3 2 System Specifications 6 3 3 Optional Add Ons 7 3 4 Spray Control Panel Options 8 4 System Hook Up 9 4 1 Connections 9 4 2 Watlow Controller 11 5 Operation 12 5 1 System...

Page 3: ...orrectly ATTENTION Supplementary information for the user draws attention to possible problems SECTION 2 SAFETY 2 1 GENERAL SAFETY INFORMATION READ AND FOLLOW INSTRUCTIONS All safety related and opera...

Page 4: ...NG Fluids under pressure can penetrate skin and cause severe injury ATTENTION Always remember to carefully read the chemical manufacturer s labels follow SDS and all directions WARNING OF SHOCK HAZARD...

Page 5: ...ration An immersion heater maintains the temperature set point of the heated fluid and by extension the process fluid A pressure gauge high limit switch turns the heater off at 650 F for fail safe pro...

Page 6: ...Humidity Range 5 to 95 non condensing Enclosures NEMA 4 Weight Control Panel tank skid 360lb empty Dimensions 58 H x 45 L x 35 D Level Switches TDR Time Domain Reflectometry Level Sensor 4 F to 302 F...

Page 7: ...Supply Unit and requires a level sensor connection to attach to the control panel The level sensor displays the current tank level as a percent to full The refill setpoint can be adjusted for user pr...

Page 8: ...nel 1000 is only capable with electric actuated spray nozzles and air nozzles can only work with a single channel Features AutoJet 1000 AutoJet 1750 AutoJet 2150 HMI Touch Screen 4 3 4 3 7 Power Input...

Page 9: ...keted hose to the components at the base of the tank then exit at the top of the tank and returns to the standpipe This allows for air relief of the conditioning circuit at that connection When initia...

Page 10: ...10...

Page 11: ...to Refill on indicator when indicator is on Auto Refill is filling the tank Low Level indicator when indicator is on indicates the level in the tank is below the low level setpoint Heater controller u...

Page 12: ...begin building pressure 9 Once the small yellow light on the sensor is lit allow the system to continue to fill for several minutes Wait until the inlet regulator at the top of the standpipe levels of...

Page 13: ...ller on the front panel Once the system is filled and the condition ing fluid is circulating properly turn on the heater Wait until the system reaches the desired setpoint At this point the fluid has...

Page 14: ...the tank has been initially filled and given the values in the above table as the system is being used the level in the tank will decrease Once the fluid reaches 250 mm from the bottom of the probe 63...

Page 15: ...the PulsaJet gun s 6 Verify Trigger signal 7 Fluid may have solidified in supply lines reconfigure heating supply or increase temperature 8 Check nozzle for clogging 3 Conditioning Fluid pressure low...

Page 16: ...ure if necessary Every 6 Months Tighten all screw terminal connections to insure proper bonding Every 12 Months Check component calibration and re calibrate if required See individual control componen...

Page 17: ...gle phase 3450rpm 56C 60hz CP12290 7 SS Strainer Screen 200 Mesh SS TE00TM4341 Sensor temperature RTD 1 2 NPT 150mm tip length 40 302F range 316 stainless steel 4 pin micro DC connector HT00BEN314S6C2...

Page 18: ...one 1 year on non wear parts from ship date Wear items are covered for manufacturing defect only for a period of one 1 year Wear items include but may not be limited to Liquid pump and Liquid regulat...

Reviews: