12
SET UP ALARM TYPES/SIDES
Alarm Types:
•
process: alarm set points are set directly
•
deviation: alarm set points are relative to the control loop
’
s set point.
•
Off: no alarm occurs
Alarm Sides:
Alarm sides allow you to set a high alarm, a low alarm, or both.
•
high: alarm when process is above high alarm set point.
•
low: alarm when process is below low alarm set point.
•
both: high and low alarms are active.
SETTING UP ALARM TYPE
1.
From Home, tap the forward arrow to go to Operations, then scroll to and select Setup.
2.
Scroll to and select Alarm.
3.
Scroll to and select Alarm 1, 2, 3, or 4.
4.
Scroll to and select Alarm Type.
5.
Scroll to and select the type: process, deviation, or off
SETTING UP ALARM SIDES
1.
Use the
back arrow
to return to
Alarm 1, 2, 3, or 4
.
2.
Scroll to and select
Alarm Sides
.
3.
Scroll to and select the desired sides option:
high, low, or both
.
4.
Use the
back arrow
to return to the Alarm list.
5.
Scroll to the
Alarm High Set Point
or
Alarm Low Set Point
, as necessary for your sides selection.
-
Repeat steps for remaining alarms
•
During normal operation, the temperature controller will display the current temperature in the Upper Display
and the current temperature setpoint in the lower display. Use the Up and Down Arrows to adjust the tempera-
ture setpoint.
Alarm Types
Alarm Sides
Figure 1
Figure 2