2-WIre standard

The 2-wire Standard configuration translates the output signal from the turbine flowmeter’s pickup coil into a current 

value. The 2-wire Standard configuration produces an output signal using a resistor to convert the electrical current 

variations into voltages. In this configuration, the power supply travels on the signal wire. 2-wire connections are 

effective transmitting the signal over long distances. 

To connect the SP714-S2i for 2-wire Standard:

1.  Remove the SP714-S2i housing cover.

2.  Pull the SP714-S2i board from the housing for access to the TB1 terminal block and the S1 switches.
3.  Attach proper cable glands and/or conduit connectors to the SP714-S2i, the pulse acquisition device, and DC power supply.

4.  Run the wires (through proper conduit) between the SP714-S2i, the pulse acquisition device, and DC power supply.

5.  Set the first S1 switch to the 

ON position and the second S1 

switch to the OFF position.

6.  Splice the resistor onto the +V 

leg from the DC power supply. 

The value of the resistor can be 

determined using the information below.

7.  Wire the SP714-S2i to the pulse 

acquisition device and DC 

power supply as indicated in the   

schematic.

8.  If necessary, adjust the input 

signal sensitivity (R1), activate 

the diagnostic test oscsillator 

(SW2), and/or check the 

diagnostic operational LEDs (D1 

& D2). 

See page 11.

9.  Coil the wires underneath the 

CPU board and place the board 

inside the housing, ensuring 

the wires are not pinched, and 

replace the housing cover.

2-WIre standard WIrInG

S1

ON

ON

1 2

GND

  1

Signal

+V

0V

Signal Ground

Cable Shield

Resistor (R

P

)

Two

Conductor

Shielded

Cable

Position 1 - ON

Position 2 - OFF

ON

ON

1 2

Electronic Register 

or 

Flow Computer

Z

 

input resistance

DC Power

Supply

Chassis GND

S1

TB1

INTERNAL OPERATING PRINCIPLE

3 2 1

2 1

TB2

Pickup Coil Signal

TB1

3 2 1

Connect Chassis GNDs at pulse acquisition device only

If the total system resistance in a 2-wire standard 

configuration exceeds the recommended value, the 

preamplifier may function irregularly as a result of 

insufficient supply voltage to the terminals.

!

 

cautIon

 

!

sP714-s2i connections

Pulse Acquisition Device

Signal

Signal Ground

Sponsler IT 400

TB2 (

1)

TB2 (

2)

LectroCount 
LCR-II/LCR 600

J8 (

33)

J8 (

37)

Toptech MultiLoad

TB2B (V+ 

any)

TB2B (V COM 

any)

Maximum Cable Length: 

380 m (1200’)

Minimum Wire Gauge: 

0.75 mm

2

 (18 AWG)

• 

Maximum cable wire resistance must be less than 

30 Ω

 

R

cable

 = R

w

1

 + R

w

2

  (both wires in cable)

• 

Total system resistance with +24 VDC power supply must be between 

250

 and 

400 Ω

       

R

system

 =  R

cable

 + R

P

• 

Maximum System Current

   

I

max

 = 

90 

m

A           

I

max

 =

• 

Resistor (

R

P

) Power Dissipation

   

P

Rd

 =

Resistor Value - 2-wire Standard

(V

dc

)

2

Rp

V

dc

R

system

24 VDC Power Supply: 

R

p

 = 330 Ω, 2 W

12 VDC Power Supply: 

R

p

 = 150 Ω, 2 W

Recommended Resistor Value (R

p

)

8

Summary of Contents for SP714-S2i

Page 1: ...Liquid Controls Group An IDEX Fluid Metering Business Sponsler SP714 S2i Pulse Amplifier Installation Parts Operation EM700 10...

Page 2: ...strictly in the hands of the owner operators of the equipment Neglect of that responsibility is not within the control of the manufacturer NOTICE The most current English versions of all Liquid Contr...

Page 3: ...fire department state and local codes to ensure adequate preparation Read this manual as well as all the literature provided in your owner s packet Save these instructions for future reference Failur...

Page 4: ...40 to 176 F 40 to 80 C Storage 76 to 257 F 60 to 125 C Specifications Input Voltage 6 28 VDC 83 mA maximum 24 VDC Protected against polarity reversal Signal Input Frequency 2 kHz maximum over operatin...

Page 5: ...y voltage Vcc 4 28 VDC Total System Resistance 500 minimum 28 VDC Output Voltage Logic HIGH Vcc 1 VDC Logic LOW 0 25 VDC Output Current Logic HIGH 8 to 60 mA DC Logic LOW 8 mA DC DC power supply volta...

Page 6: ...eratures above 70 C use field wiring suitable for 20 C above maximum ambient temperature II Suitable for use in surface not mine installations 2 G High level of protection is provided against flammabl...

Page 7: ...uration translates the output signal from the turbine flowmeter s pickup coil into a current value 2 wire connections are effective transmitting the signal over long distances The 3 wire TTL Sourcing...

Page 8: ...llator SW2 and or check the diagnostic operational LEDs D1 D2 See page 11 9 Coil the wires underneath the CPU board and place the board inside the housing ensuring the wires are not pinched and replac...

Page 9: ...using the information below 7 Wire the SP714 S2i to the pulse acquisition device and DC power supply as indicated in the schematic 8 If necessary adjust the input signal sensitivity R1 activate the di...

Page 10: ...n the schematic 8 If necessary adjust the input signal sensitivity R1 activate the diagnostic test oscsillator SW2 and or check the diagnostic operational LEDs D1 D2 See page 11 9 Coil the wires under...

Page 11: ...equency is above 40 Hz the light will flash very quickly and the LED will appear to be constantly illuminated If the input into the SP714 S2i stops on a positive portion of the signal pulse the LED wi...

Page 12: ...rive Lake Bluff IL 60044 847 295 1050 SAMPI Via Amerigo Vespucci 1 55011 Altopascio Lucca Italy 39 0583 24751 IDEX Fluid and Metering Pvt Ltd Survey No 256 Alindra Savli GIDC Manjusar Dist Vadodara 39...

Reviews: