IM-P014-23
EMM Issue 4
32
IECEx
certification
Equipment protection level IECEx certificate : IECEx SIR 15.0070X
Gas
Ex ia op is IIC T4 Ga
Dust
Ex ia IIIC op is T135 °C Da
Tamb
-20 to +70 °C
Tprocess
-20 to +427 °C (heat shield must be fitted for higher
temperatures, see Note 1 below).
For use with: Tadiran SL-2880 3.6 V Lithium Thionyl Chloride Battery only.
Standards used
IEC 60079-0, IEC 60079-11 and IEC 60079-28
European
certification
ATEX Intrinsic Safety
ATEX certificate : Sira 15ATEX2197X
Gas
Ex ia op is IIC T4 Ga
Dust
Ex ia IIIC op is T135 °C Da
Tamb
-20 to +70 °C
Tprocess
-20 to +427 °C (heat shield must be fitted for higher
temperatures, see Note 1 below).
For use with: Tadiran SL-2880 3.6 V Lithium Thionyl Chloride Battery only.
Standards used
EN 60079-0, EN 60079-11 and EN 60079-28
Note 1:
For higher process and ambient temperatures the head and heat shield must be installed as detailed
in Sections 3.3 and 3.4.
Warning:
1. The equipment must be inspected and cleaned regularly to prevent the build-up of dust on
the product.
2. Electrostatic Hazard – Wipe only with a damp cloth.
3. Only Tadiran SL-2880 3.6 V Lithium Thionyl Chloride batteries are permitted to be used within
the STAPS wireless steam trap monitor.
4. The enclosure is manufactured from aluminium. In rare cases, ignition sources due to impact
and friction sparks could occur. This shall be considered during installation, particularly if
the equipment is installed in a zone 0 location.
Note:
The above certification and approvals are only valid if the product is installed using the genuine
supplied component parts and accessories, including consumable items such as batteries.
Certfication
5. Certification and approvals