10
IM-P087-33 MI Issue 6
Table 11 R1C normal operation
Trap status
Status lights
Trap operating correctly
Red and orange lights Off
Green light Flashing
Trap leaking steam
Red light On Green light Flashing
Trap blocked or waterlogged
Orange light On Green light Flashing
Trap cold but free of condensate
(this is a common state during system
Red and Orange lights On
start-up or when the system is shut-down)
Green light Flashing
or sensor wires disconnected.
During normal operation, the green light flashes On every second to show that electrical power
is connected to the R1C and that it is operating correctly.
If the green light is not flashing, there may be a problem with the R1C.
The R1C will show a failure for as long as the fault is present. If the R1C detects a transient fault,
it will show the failure for at least one minute.
6. Normal operation