5.3 Probe clearance record sheet
We strongly recommend that a record of the probe clearance test is kept, and a sheet is provided
for this purpose. This must be completed each time the probe is fitted/refitted.
How to complete the sheet:
-
Date:
The date the test procedure was carried out.
-
Reason for test:
Initial installation or annual inspection.
-
Clearance 14 mm (
"):
A signature in this box signifies the test has been successfully
completed, verifying the tip clearance is greater than 14 mm ( ").
-
The (competent) person who did the tests must sign this box.
Verification Signatures
Clearance
Checking
Date
Reason for test
14 mm ( ") wires Independent
or more
removed
assessor