LCR2250 Level Controller
4.7 Connection of level transmitter
The LCR2250 level controller can be combined with the LP20/LP21/PA420 level transmitter.
For connecting the equipment, please use a screened, multi-core control cable with a minimum conductor
size of 0.5 mm2, e.g. LiYCY 2 x 0.5 mm
2
, maximum length 100 m.
Connect the screen as shown in the wiring diagram (Fig. 4).
Important
-
Please commission the equipment as described in the LP20/LP21/PA420
installation & operating manuals.
-
Route the connecting cable between items of equipment separately from power
lines.