9. Maintenance
Many faults which occur on commissioning are found to be due to incorrect wiring or setting up,
so we recommend that a thorough check is first carried out should there be a problem.
If this has been done and the controller is still not working, make the following checks:-
10.1 Display not lit - check:
-
Correct voltage selected.
-
Live supply connected.
-
Neutral connected.
-
Fuse not blown.
10.2 If a PA20 amplifier is used, check:
-
Probe output voltage is between 0 V and 6 Vdc across terminals 7 and 9 of the controller
(or terminal 2 and earth on the probe).
-
Probe supply voltage is between 15 Vdc and 35 Vdc across terminals 7 and 8 of the
controller (or terminal 1 and earth on the probe).
-
Preamplifier sensitivity is correctly set. (See PA20 IMI).
10.3 If a 4 - 20mA input is used, check:
-
Loop connections not reversed - (polarity incorrect).
10.4 Valve fails to function correctly when proportional
(modulating) control is selected (EL5600):
-
Check that the potentiometer wiring is correct. Voltage across terminals 1 and 2 of the
controller should vary from 0 V (valve closed) to 2.1 Vdc (valve open). This voltage can also
be measured across terminals 14 and 15 of the potentiometer.
10.5 To check that the alarms are functioning:
-
Deliberately set them above / below the actual water level.
10.6 To check that the feedwater valve and relays are operating:
-
Select 'Manual' and use the '<' and '>' buttons to actuate the valve.
10.7 Display indicates both ALARM HIGH and ALARM LOW at
the same time:
-
Alarm levels incorrectly set -
Both high and low alarms must be set to operate outside the control band.
or:-
If the LVLINPUT O/RNGDET feature has been selected:-
-
Level input out of range -
This is most likely to be due to a faulty connection.
The LC2610 needs no special servicing or maintenance. Boiler water level controls and alarms
do, however, need regular testing and inspection. General guidance for the UK is given in
Health and Safety Executive Guidance Note PM5.
For specific instructions for Spirax Sarco systems see separate literature.