11
Pressure bar g
Te
m
pe
rat
ur
e °C
C
A
The product
must not
be used in this region.
This product should not be used in this region as damage to the internals may occur.
For ASME 150 Flange
PMA Maximum allowable pressure
19.6 bar g @ 38 °C
TMA Maximum allowable temperature
300 °C @ 10.2 bar g
PMO Maximum operating pressure
13.9 bar g @ 198 °C
Note:
For lower operating
temperatures consult
Spirax Sarco
TMO Maximum operating temperature
266 °C @ 11.5 bar g
TMO Maximum operating temperature
300 °C @ 10.2 bar g
When fitted with a bimetallic air vent
Cold hydraulic test pressure of :
29.4 bar g
For ASME 300 Flange
PMA Maximum allowable pressure
40 bar g @ 100 °C
TMA Maximum allowable temperature
300 °C @ 27.5 bar g
PMO Maximum operating pressure
31.4 bar g @ 238 °C
Note:
For lower operating
temperatures consult
Spirax Sarco
TMO Maximum operating temperature
284 °C @ 28.5 bar g
TMO Maximum operating temperature
300 °C @ 27.6 bar g
When fitted with a bimetallic air vent
Cold hydraulic test pressure of :
60 bar g
D
PMX
Maximum
differential
pressure
Size
DN15, DN20, DN25 DN40, DN50
FT44-4.5
4.5 bar
4.5 bar
(65 psi)
FT44-10
10 bar
10 bar
(145 psi)
FT44-14
14 bar
-
(203 psi)
FT44-21
21 bar
21 bar
(304 psi)
FT44-32
32 bar
32 bar
(464 psi)
Note:
With internals fitted, test pressure must not exceed
D
PMX
Caution:
The trap in its complete operational form must not be subjected to a pressure greater
than 48 bar otherwise damage to the internal mechanism may result.
B
Pressure psi g
Te
mp
era
tu
re
°
F
Steam
saturation
curve
Pressure / temperature limits
A
-
B
Flanged
ASME 300
A
-
C
Flanged
ASME 150