Spirax Sarco AE50S Installation And Maintenance Instructions Manual Download Page 7

IM-P017-11 

 CMGT Issue 4

7

Discharge to 

safe visual 

point

Air bottle

Fig. 2 Typical application

Note: Before actioning any installation observe the 'Safety information' in Section 1.

Refering  to  the  Installation  and  Maintenance  Instructions,  name-plate  and  Technical 

Information Sheet, check that the product is suitable for the intended installation:

3.1

Check  materials,  pressure  and  temperature  and  their  maximum  values.  If  the 

maximum operating limit of the product is lower than that of the system in which 

it is being fitted, ensure that a safety device is included in the system to prevent 

overpressurisation.

3.2

Determine the correct installation situation and the direction of fluid flow.

3.3

Remove protective covers from all connections.

3.4

The AE50S should be installed vertically with the inlet at the bottom. Because of 

the way automatic air and gas vents operate they all dribble water and liquid when 

discharging air and gas. This is perfectly normal. 

We recommend piping the discharge to a safe visible point or drain via an air break.

3.5

For installation on superheated water

 

applications:

 We at Spirax Sarco 

recommend 1 to 2 m of 

¾

" vertical pipeline should be fitted prior to the inlet of the vent. 

On superheated water systems the outlet pipework must be sized to accommodate 

any flash steam created during discharge. 

Direct the outlet pipework to a safe point of discharge where there is no risk of injury 

to persons or damage to property.

3. Installation

Because of the way automatic air vents operate they all 

dribble water when discharging air. This is perfectly normal, 

because of this we recommend piping the discharge to a 

drain via an air break.

Summary of Contents for AE50S

Page 1: ...General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Copyright 2017 Printed in GB IM P017 11 CMGT Issue 4 0176050 4 AE50S Automatic Air and Gas Vent for...

Page 2: ...been specifically designed for use on steam air or water condensate which are in Group 2 of the above mentioned Pressure Equipment Directive ii Check material suitability pressure and temperature and...

Page 3: ...ed valves Do not assume that the system has depressurised even when the pressure gauge indicates zero 8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns If...

Page 4: ...mitted operating conditions the surface temperature of some products may reach temperatures of 100 C 212 F Many products are not self draining Take due care when dismantling or removing the product fr...

Page 5: ...roduct is available with material certification EN 10204 3 1 B for bowl cover and inlet connection as standard Note For further information see the following Technical Information Sheet TI P017 10 whi...

Page 6: ...g TMA Maximum allowable temperature 427 C 800 F PMO Maximum operating pressure 41 4 bar g 600 psi g TMO Maximum operating temperature 427 C 800 F PMX Maximum differential pressure 30 bar 435 psi Desi...

Page 7: ...onnections 3 4 The AE50S should be installed vertically with the inlet at the bottom Because of the way automatic air and gas vents operate they all dribble water and liquid when discharging air and g...

Page 8: ...to pass through the main valve As soon as water reaches the vent the float is raised and the lever mechanism closes the valve When more air reaches the vent it displaces water and the float falls thu...

Reviews: