This section lists the specifications for the Type D50 pressure regulator. Factory specifications are stamped on the 

nameplate fastened on the regulator at the factory.

Valve Temperature Rating

(1)

Stainless steel Disk

Cast iron: 

400°F / 204°C

Teflon

®

 Disk

Cast iron: 

300°F / 149°C

Main Valve Material

Cast iron

Approximate Weight

3.6 to 13.6 lbs / 8 to 30 kg

Valve Sizes

NPS 1/2, 3/4, 1, 1-1/4, 1-1/2 and 2 / 

 

DN 15, 20, 25, 32, 40 and 50

End Connection Styles

NPT and BSPT

Valve Pressure Rating

(1)

Stainless steel Disk

Cast iron: 

200 psig / 13.8 bar

Teflon

®

 Disk

Cast iron: 

300 psig / 21.0 bar

1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Principle of Operation

The Type D50 is a direct-operated regulator. 

Downstream pressure is registered through the control 

ports to the under side of the diaphragm. As the 

pressure on diaphragm approaches a balance with the 

force exerted by the adjusting spring, disk is throttled 

to a position where just enough fluid flows to maintain 

the set delivery pressure.

Intended Purpose

The Type D50 Direct Acting Pressure Regulator 

is a compact, moderately priced steam, water or 

gas regulator intended to satisfy most fundamental 

requirements for pressure reduction.

Teflon

®

 is a mark owned by E.I. du Pont de Nemours and Co.

Installation

 

 WARNING

Personal injury or system damage 

may result if this regulator is installed, 

without appropriate overpressure 

protection, where service conditions 

could exceed the limits given in 

the Specifications section and/or 

regulator nameplate.

Additionally, physical damage to the 

regulator may result in personal injury 

or property damage due to escaping of 

accumulated gas. To avoid such injury 

and damage, install the regulator in a 

safe location.
Under enclosed conditions or indoors, 

escaping gas may accumulate and be an 

explosion hazard. In this case, the vent 

should be piped outdoors.
For regulator constructions with a 

spring case vent, the vent should be 

kept open to permit free flow of gas 

to the atmosphere. Protect openings 

against entrance of rain, snow, insects 

or any other foreign material that may 

plug the spring case vent or vent line.
All pressure equipment should be 

installed in a non-seismic area; 

should not be exposed to fire; and 

should be protected from thunderbolt 

(lightning) strikes.

2

Type D50

Summary of Contents for D50

Page 1: ... result in a hazardous condition Installation operation and maintenance procedures performed by unqualified personnel may result in improper adjustment and unsafe operation Either condition may result in equipment damage or personal injury Only a qualified person shall install or service the Type D50 pressure regulator Introduction Scope of the Manual This manual provides instructions for the inst...

Page 2: ... Intended Purpose The Type D50 Direct Acting Pressure Regulator is a compact moderately priced steam water or gas regulator intended to satisfy most fundamental requirements for pressure reduction Teflon is a mark owned by E I du Pont de Nemours and Co Installation WARNING Personal injury or system damage may result if this regulator is installed without appropriate overpressure protection where s...

Page 3: ...NAL TEFLON DISK FOR LIQUID AND GAS SERVICE TEFLON DISK ASSEMBLY 2 DISK 1 BOTTOM PLUG GASKET 1 The above parts are all that are available 1 Parts contained in repair kit 2 Parts substituted in Teflon repair kit Figure 2 Type D50 Operational Schematic Teflon is a mark owned by E I du Pont de Nemours and Co 3 Type D50 ...

Page 4: ...re 4 7 Install initial and delivery pressure gauges to indicate performance When long runs of piping Installing the Valve 1 Flush the piping system thoroughly to clear it of any debris 2 Mount the valve between unions with the arrows under the diaphragm flange pointing in the direction of the flow Figure 3 Aspirator Location Mark NORMAL POSITION ASPIRATOR LOCATION MARK ADJUSTED POSITION are involv...

Page 5: ...SSURE STEAM MAIN WHEN REDUCTION IN NOISE LEVEL IS IMPORTANT AT LEAST 10 PIPE DIAMETERS D1 STRAIGHT RUN FULL SIZE AT LEAST 20 PIPE DIAMETERS D2 TO FIRST TURN SECONDARY PRV OR CONTROL VALVE SAFETY VALVE LONG RADIUS ELBOW TYPE D50 REGULATOR 2 Failure to close or over riding delivery pressure a Adjusting spring key 6 may have been tampered with b Bypass valve may be leaking or open c Valve diaphragm m...

Page 6: ...disassembling the valve first remove the compression from the adjusting spring 4 Minor damage to the seat ring and disk may be repaired by light grinding with 400 grit or finer lapping compound 5 Before reassembling the valve the old gasket material and sealing compound should be removed Metal to metal joints should be sealed with Copalite Permatex or equal plastic gasket compound compatible with ...

Page 7: ...1 2 3 4 5 6 7 8 9 10 11 12 22 13 14 15 16 17 23 24 21 20 19 18 Figure 5 Type D50 Assembly 7 Type D50 ...

Page 8: ...scribed herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Electric Co does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintena...

Reviews: