3-4
Chapter 3: Configuring the 1762sc-OF8 for RSLogix 50
User’s Manual Pub. 0300246-01 Rev. C
WARNING
Each command issued will have a corresponding module response in the
input data file. See Section 3.5.1 for more information.
WARNING
For proper operation, during the 600 ms delay, the output words should be
set to the correct command values to avoid sending erroneous analog
signals.
3.4.1
Output Data File (Command Mode)
The output data file is used to configure each channel for the OF8 as well as
control the output signal of each channel. Use the addressing scheme below to
locate the 8 output words needed to configure the module.
Figure 3-2 (Output Addressing Scheme)
1.
I/O located on the controller (embedded I/O) is slot 0. I/O added to the
controller (expansion I/O) begins with slot 1.
The module enters a special mode called Command Mode when the PLC
transitions from Program mode to Run mode. When the module enters
Command Mode, the output file is used to send commands to the module and the
module responds via the input data file. The table below shows the layout for
each output word during both modes of operation. See Table 3-6 for command
mode response data.