background image

 

Installing the Detector 

 

3.6.1 

Tilt Mount Assembly 

Figure 4 shows the tilt mount assembly. 

 

 

Figure 4: Tilt Mount Assembl

Figure 5 shows the tilt mount assembly with dimensions in both millimeters and 
inches. 

 

Figure 5: Tilt Mount Assembly (dimensions in millimeters and inches) 

Tilt holding 
plate 

Tilt mount 

Horizontal 
locking screw 

Detector holding 
plate 

Vertical locking 
screw 

Summary of Contents for SharpEye 40/40R

Page 1: ...Model 40 40R Single IR Flame Detector User Guide 8200 Market Blvd Chanhassen MN 55317 USA Phone 1 973 239 8398 Website www spectrex net Email spectrex csc rmtna emerson com ...

Page 2: ......

Page 3: ...ion or any use of any product or circuit described herein neither does it convey license under its patent rights or the rights of others Warranty SPECTREX agrees to extend to Purchaser Distributor a warranty on the SPECTREX supplied components of the SharpEye products SPECTREX warrants to Purchaser Distributor that the products are free from defects in materials and workmanship for a period of fiv...

Page 4: ......

Page 5: ... 18 2 4 2 Heated Optics 19 2 4 3 HART Protocol 19 2 4 4 RS 485 Modbus 19 2 4 5 Product Certification 20 2 5 Performance Considerations 22 2 5 1 Detection Sensitivity 22 2 5 2 Cone of Vision 23 2 5 3 False Alarm Prevention 24 2 5 4 Visual Indicators 24 2 5 5 Output Signals 25 2 5 6 Detector Status 26 2 5 7 Auxiliary Relay as End of Line 28 2 6 Internal Detector Tests 28 2 6 1 Continuous Feature Tes...

Page 6: ...g the Detector 40 3 7 1 Verifying the Detector Wiring 42 3 8 Configuring Your Detector 43 3 8 1 Alarm Delay 44 3 8 2 Address Setup 44 3 8 3 Function Setup 44 3 8 4 Heated Optics 45 4 Operating the Detector 47 4 1 Powering Up 47 4 2 Safety Precautions 47 4 2 1 Default Functions Settings 48 4 3 Testing Procedures 48 4 3 1 Automatic BIT Test 49 4 3 2 Manual BIT Test 49 4 3 3 Testing with Flame Simula...

Page 7: ...entries 58 A 5 5 Dimensions 58 A 5 6 Weight 58 A 6 Environmental Specifications 58 A 6 1 High Temperature 58 A 6 2 Low Temperature 58 A 6 3 Humidity 58 A 6 4 Salt Fog 58 A 6 5 Dust 59 A 6 6 Vibration 59 A 6 7 Mechanical Shock 59 A 6 8 Electromagnetic Compatibility EMC 59 Appendix B Wiring Instructions 61 B 1 General Instructions for Electrical Wiring 61 B 2 Calculation Formula 62 B 3 Typical Wirin...

Page 8: ...eral 73 D 2 2 Electrical 73 D 2 3 Physical 73 D 2 4 EMI Compatibility 74 D 3 Tilt Mount 75 D 4 Duct Mount 76 D 5 Weather Cover 77 D 6 Air Shield 78 Appendix E SIL 2 Features 79 E 1 40 40R Flame Detector 79 E 1 1 Safety Relevant Parameters 79 E 1 2 Guidelines for Configuring Installing Operating and Service 79 Appendix F End of Line Resistor 81 Technical Support 84 ...

Page 9: ...r 2 Wiring 64 Figure 9 0 20mA Wiring Option 1 Sink 4 Wire Default 64 Figure 10 0 20mA Wiring Option 1 Converted to Source 3 Wire 65 Figure 11 0 20mA Wiring Option 1 Non isolated Sink 3 Wire 65 Figure 12 0 20mA Wiring Option 2 and 3 Source 3 Wire available with the HART Protocol 66 Figure 13 RS 485 Networking 67 Figure 14 Flame Simulator FS 1300 69 Figure 15 Flame Simulator Battery Replacement 71 F...

Page 10: ...BIT 31 Table 11 Results of an Unsuccessful Manual BIT 31 Table 12 Tools 35 Table 13 Model 40 40R Wiring Options 42 Table 14 Functions 44 Table 15 Default Function Values 48 Table 16 Results of Successful Flame Simulator Test 49 Table 17 Troubleshooting Table 52 Table 18 Electrical Specifications 54 Table 19 Contact Ratings 55 Table 20 20mA Current Output 55 Table 21 Electromagnetic Compatibility E...

Page 11: ...tector including preparations before installation wiring and mode settings Chapter 4 Operating the Detector describes how to power up and test the detector The chapter also lists safety precautions you should take when operating the detector Chapter 5 Maintenance and Troubleshooting describes basic maintenance troubleshooting and support procedures Appendix A Specifications lists the detectors tec...

Page 12: ... Ian Buchanan Eric Zinn 5 February 2013 Sixth Release Ian Buchanan Eric Zinn 6 February 2015 Seventh Release Ian Buchanan Eric Zinn 7 June 2015 Eighth Release Ian Buchanan Eric Zinn 8 January 2016 Ninth Release Ian Buchanan Eric Zinn 9 July 2016 Tenth Release Ian Buchanan Eric Zinn 10 October 2016 Eleventh Release Jay Cooley Ian Buchanan 11 January 2017 Twelfth Release Jay Cooley Ian Buchanan 12 F...

Page 13: ...ce EOL End of Line FOV Field of View HART Highway Addressable Remote Transducer communications protocol IAD Immune at Any Distance IECEx International Electro Technical Commission Explosion IP Internet Protocol IPA Isopropyl Alcohol IR Infrared IR3 Refers to the 3 IR sensors in the VID JP5 Jet Fuel LED Light Emitting Diode MODBUS Serial communications protocol using Master Slave messaging N A Not ...

Page 14: ...ations This section explains and exemplifies the usage of warnings cautions and notes throughout this guide Warning This indicates a potentially hazardous situation that could result in serious injury and or major damage to the equipment Caution This indicates a situation that could result in minor injury and or damage to the equipment Note This provides supplementary information emphasizes a poin...

Page 15: ...ration of the sensors and the respective circuits Do not attempt to modify or repair the internal circuits or change their settings as this will impair the system s performance and void the SPECTREX product warranty The SharpEye 40 40 detector is designed to operate as a stand alone unit directly connected to an alarm system or an automatic fire extinguishing system The detector can also be a part...

Page 16: ...equired approval The configuration detail is included in the product part number on the product label and takes the form 40 40R XXXXX where XXXXX defines the model according to the above requirements To modify the default or pre ordered configuration and perform maintenance tasks please refer to the HART Protocol TM777030 the RS 485 Manual TM777050 or TM777060 The P Ns are defined as Note Aluminum...

Page 17: ... O RS 485 5 Power Manual BIT Fault Relay N O Alarm Relay N O Auxiliary N O RS 485 Note Wiring option 1 is the default The mA sink output can be altered to source type with a link between Terminals 1 and 8 No other wiring options can be changed onsite For example product number 40 40R 321SC has the following options Wiring Option 3 Power Manual BIT RS 485 0 20mA Source with the HART protocol Fault ...

Page 18: ...ed per FM3260 Accessories are approved as part of ATEX and IECEx approval 2 4 Principles of Operation This section describes the principles of operation for the 40 40R 2 4 1 Hydrocarbon Fire Detection The Single IR flame detector provides early warning of flaming fires involving organic materials hydrocarbon fuels and vapors These fires emit strong IR radiation in the 4 4 micron spectral band wher...

Page 19: ...RT protocol HART Communication is a bi directional industrial field communication protocol used to communicate between intelligent field instruments and host systems HART is the global standard for smart process instrumentation and the majority of smart field devices installed in plants worldwide are HART enabled HART is available in wiring options 1 2 and 3 see Table 1 HART technology is easy to ...

Page 20: ...IC T4 Gb Ex tb op is IIIC T106 C Db 55 C Ta 85 C The accessories tilt mount P N 40 40 001 weather cover P N 777163 and P N 777268 duct mount P N 777670 and air shield P N 777650 are included in the approval This product is suitable for use in hazardous Zones 1 and 2 with IIC gas group vapors present and Zones 21 and 22 with IIIC dust type present 2 4 5 2 FM CSA The 40 40R Optical Flame Detector is...

Page 21: ...etector has been tested and approved per EN54 10 by VdS This test includes a functional test environmental test EMI EMC test and software check For more details see VdS Report No BMA 13110 2 4 5 5 Inmetro UL The 40 40R Flame Detector is in compliance with the standards ABNT NBR IEC 60079 0 ABNT NBR IEC 60079 1 ABNT NBR IEC 60079 7 ABNT NBR IEC 60079 18 ABNT NBR IEC 60079 31 and INMETRO decree No 1...

Page 22: ...g Pre alarm Alarm The detection distance for the warning level is approximately 10 higher than for the alarm distance The detection distance for the alarm level is 50ft 15m from a standard fire For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for the detector is 0 005 1 m Note Zeta parameters may vary significantly with changes in temperature air pressure humidity visib...

Page 23: ...asoline 50 15 N Heptane 50 15 LPG 43 13 JP5 37 11 Kerosene 37 11 Diesel Fuel 37 11 Polypropylene 37 11 Methane 29 5 9 Alcohol 95 25 7 5 IPA 25 7 5 Methanol 25 7 5 Paper 20 6 30 0 75m high 10 0 25m width plume fire 2 5 2 Cone of Vision Horizontal 90 Vertical 90 Figure 1 Field of View ...

Page 24: ...light with white enamel reflector standard office or shop 70W or 2 35W IAD Arc welding 6mm 5 16 rod 210A 11 5 3 5 Grinding metal 1 7 0 5 Lit cigar 3 3 1 Lit cigarette 1 7 0 5 Match wood stick including flare up 3 3 1 Notes IAD Immune at Any Distance All sources are chopped from 0 20Hz 2 5 4 Visual Indicators One 3 color LED indicator is located inside the detector window as shown in Figure 2 The d...

Page 25: ...efault configuration or the wiring options selected for the 40 40R detector Determine the outputs for your model according to Table 5 The detector incorporates several types of output suitable to different control systems 0 20mA stepped with HART Relays alarm fault auxiliary RS 485 Modbus Indicator LED ...

Page 26: ...with the HART protocol RS 485 All versions Modbus protocol 2 5 6 Detector Status The possible detector function statuses are listed in Table 6 A more detailed fault analysis can be seen via HART or RS 485 Table 6 Detector Status Status Description Normal Normal operation BIT Built In Test being performed Warning Fire detected changed to Warning pre alarm state Alarm Fire detected changed to Fire A...

Page 27: ...detected 2 The alarm state can be optionally latched via programmed function default is non latched 3 The detector will remain in BIT Fault state until it has passed a successful BIT 4 The auxiliary relay can be activated at the warning level or alarm level depending on programmed function Note The outputs depend on the wiring options 2 5 6 1 Optional Latching Alarms are set as non latching by def...

Page 28: ...red 2 6 Internal Detector Tests The detector performs 2 types of self tests Continuous Feature Test page 28 Built In Test BIT page 29 2 6 1 Continuous Feature Test During normal operation the detector tests itself continuously and indicates a fault if a failure is found This type of test complies with SIL 2 requirements The detector continuously tests Input voltage level All internal regulator vol...

Page 29: ...ector s Built In Test BIT also checks the following Electronic circuitry Sensors Window cleanliness The detector can be set to perform the BIT in the following modes Automatically and manually Manually only Note In Manual BIT the outputs may also be tested and Control System inhibit should be applied if this could initiate other systems 2 6 3 1 How the BIT Operates The detector s status remains un...

Page 30: ...ts of an Unsuccessful BIT Output Result Fault Relay Wiring options 1 2 and 4 changes to open Wiring options 3 and 5 changes to closed 0 20mA Output Wiring options 1 2 and 3 BIT fault 2mA Power LED Yellow flashing 4Hz BIT Procedure Performed every 1 minute 2 6 3 3 Manual BIT The BIT is manually initiated by momentarily connecting Terminal 3 with Terminal 2 or a switch across these terminals in the ...

Page 31: ...2 and 3 Initiates 20mA only when the function alarm BIT is set to Yes Initiates 16mA when the function auxiliary BIT is set to Yes and the function alarm BIT is set to No Power LED Green flashing 1Hz Table 11 Results of an Unsuccessful Manual BIT Output Result Fault Relay Wiring options 1 2 and 4 changes to Open Wiring options 3 and 5 changes to Closed 0 20mA Output Wiring options 1 2 and 3 Indica...

Page 32: ......

Page 33: ...ble materials 3 1 2 Wiring The wire gauge must be designed according to the distance from the detector to the controller and the number of detectors on the same power line See Wiring Instructions on page 61 To fully comply with EMC directive and protect against interference caused by RFI and EMI the cable to the detector must be shielded and the detector must be grounded The shield should be groun...

Page 34: ...ved the following contents Delivery form Flame detector Plastic weather cover User manual Quality document Tool keys per shipment Check and record the following Verify the appropriate Purchase Order Record the Part Number P N and Serial Number of the detectors and the installation date in an appropriate logbook Verify that all components required for the detector installation are readily available...

Page 35: ...al Instructions for Safe Use The dimensions of the flame paths are other than the relevant minimum or maximum as required by Table 2 of EN 60079 1 2014 as detailed below Flame Path Location Type of Joint Maximum Gap ic Minimum Length L Sapphire window Flanged 0 04mm 10 5mm Main spigot Cylindrical 0 15mm 15 5mm Gaps ic should not be modified to be any larger and lengths L should not be modified to ...

Page 36: ...re range 67 F 55 C to 185 F 85 C Installation should be carried out by suitably trained personnel in accordance with the applicable code of practice such as EN 60079 14 1997 Inspection and maintenance of this equipment should be carried out by suitably trained personnel in accordance with the applicable code of practice such as EN 60079 17 Repair of this equipment should be carried out by suitably...

Page 37: ...h the following To avoid water condensation or water in the detector install the detector with the conduits placed downward to include drain holes When using the optional tilt mount use flexible conduits for the last portion connecting to the detector For installations in atmospheres as defined in group B of the NFPA 72E seal the conduits inlets When pulling the cables through the conduits ensure ...

Page 38: ...le IR Flame Detector User Guide 3 6 Installing the Tilt Mount The tilt mount P N 40 40 001 enables the detector to be rotated up to 60º in all directions Figure 3 shows the detector mounted on the tilt mount Figure 3 Detector with Tilt Mount ...

Page 39: ...mbly Figure 4 Tilt Mount Assembly Figure 5 shows the tilt mount assembly with dimensions in both millimeters and inches Figure 5 Tilt Mount Assembly dimensions in millimeters and inches Tilt holding plate Tilt mount Horizontal locking screw Detector holding plate Vertical locking screw ...

Page 40: ...oint the detector towards the protected area and make certain that the view of the area is unobstructed Secure the detector in that position by tightening the locking screws on the tilt mount making sure the detector is in the correct position The detector is now correctly located aligned and ready to be connected to the system 3 7 Connecting the Detector This section describes how to connect the ...

Page 41: ...tor must be well grounded to earth ground Verify the wiring Warning Improper wiring may damage the detector Check the wires for secure mechanical connection and press them neatly against the terminal to prevent them from interfering while closing the back cover Figure 6 Place and secure the detector s back cover by screwing the 3 socket head screws in the cover bolts Figure 3 Earth terminal Termin...

Page 42: ...4VDC 24VDC 2 0VDC 0VDC 0VDC 0VDC 0VDC 3 Manual Bit Manual Bit Manual Bit Manual Bit Manual Bit 4 Fault Relay N C Fault Relay N C Fault Relay N O Fault Relay N C Fault Relay N O 5 6 Alarm Relay N O Alarm Relay N O Alarm Relay N O Alarm Relay N O Alarm Relay N O 7 Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay C 8 0 20mA In Alarm Relay N C Alarm Relay N C Auxiliary N O Auxiliary...

Page 43: ...ng on the function configuration the auxiliary relay may act in parallel with the alarm relay to activate another external device or it may provide a warning signal 3 8 Configuring Your Detector You can reprogram the function setup using the RS 485 connection or the HART protocol as follows USB RS 485 Harness Kit P N 794079 The USB RS 485 Harness Kit with RS 485 USB converter used with the SPECTRE...

Page 44: ...hen evaluates the condition for 3 seconds If the alarm level is still present the alarm outputs are activated If this condition no longer exists the detector returns to its standby state The alarm delay option affects the output relays and the 0 20mA The LEDs and outputs indicate warning levels during the delay time only if the fire condition exists 3 8 2 Address Setup The detector provides up to ...

Page 45: ...ry relay is used as End of Line No Auxiliary relay operates in accordance with Functions 2 and 5 default Only available in Models 40 40R 4XXXX and 5XXXX 3 8 4 Heated Optics The heated optics can be defined as one of the following modes Heated Mode Off Not operated On Continuously Auto Per temperature change In Auto mode the default Heat On setting is 41 F 5 C Heating stops when the temperature is ...

Page 46: ......

Page 47: ...z BIT is executed If successful the green LED flashes at 1Hz the fault relay contacts close and mA output is 4mA Enter Normal mode Caution The majority of detectors are used in the default non latched alarm mode Only perform a reset when the latched alarm option has been programmed To reset the detector when it is in a latched alarm state Disconnect power Terminal 1 or Terminal 2 Or Initiate a Man...

Page 48: ... not available This function is not used Automatic BIT Yes Alarm BIT No Auxiliary BIT No In wiring options 1 2 and 3 the auxiliary relay is not available This function is not used EOL No In wiring options 1 2 and 3 the auxiliary relay is not available This function is not used Heat Mode Auto Heat On 41 F 5 C The detector starts heating the window for any temperature below this value in degrees Cel...

Page 49: ...ection level As a result the detector will generate a Fire Alarm signal See Flame Simulator FS 1300 on page 69 for more information Caution If the detector is exposed to a flame simulator the alarm and accessory relays and 0 20mA are activated during the simulation Therefore automatic extinguishing systems and any external devices which may be activated during this process must be disconnected To ...

Page 50: ...ye Single IR Flame Detector User Guide Alarm Relay Activated For a few seconds and then returns to Normal Auxiliary Relay Activated For a few seconds and then returns to Normal Fault Relay Remains active during the test LED Red steady ...

Page 51: ...ions depends upon the local environmental conditions and specific applications The fire detection system designer will give his recommendations To clean the detector viewing window and reflector Disconnect power to the detector before proceeding with any maintenance including window lens cleaning Use water and detergent and then rinse the viewing window with clean water Where dust dirt or moisture...

Page 52: ...le Problem Cause Corrective Action LEDs Off Fault Relay at N O 0 20mA at 0mA No power to the unit Check that the correct power is sent to the detector Check power polarity Check wiring in the detector Send the detector back for repairs Yellow amber LED flashes at 4Hz Fault Relay at N O 0 20mA at 0mA Fault Detector Low Voltage Faulty Detector Check the voltage at the detector verify at least 24V at...

Page 53: ...Methane 29 5 9 LPG 43 13 Ethanol 95 25 7 5 Diesel Fuel 37 11 Methanol 25 7 5 JP5 37 11 IPA Isopropyl Alcohol 25 7 5 Polypropylene Pellets 37 11 Office Paper 20 6 30 0 75m high 10 0 25m width plume fire Response Time Typically 5 seconds Adjustable Time Delay Up to 30 seconds Sensitivity Ranges 2 ranges for 1ft2 0 1m2 n heptane pan fire from 15ft 5m to 50ft 15m Fields of View Horizontal 90 Vertical ...

Page 54: ...105mA 100mA Alarm 130mA 115mA Alarm when heater on 160mA 145mA A 2 1 Electrical Input Protection The input circuit is protected against voltage reversed polarity voltage transients surges and spikes according to MIL STD 1275B A 3 Outputs A 3 1 Electrical Interface There are 5 output wiring options These options are defined at the factory per the customer order and cannot be changed at the customer...

Page 55: ... relay in wiring options 1 2 and 4 is normally energized closed during normal operation of the detector The relay is de energized open in a fault condition or low voltage situation 2 In wiring options 3 and 5 the relay is normally energized open during normal operation of the detector The relay is de energized close contact in a fault condition or low voltage situation A 3 2 2 0 20mA Current Outpu...

Page 56: ...installations with computerized controllers The communications protocol is Modbus compatible This protocol is a standard and widely used It enables continuous communication between a standard Modbus controller Master device and a serial Network of up to 247 detectors A 3 3 Heated Optics The front window can be heated to improve performance in ice condensation and snow conditions The heater increas...

Page 57: ...C Ta 75 C Or Ex II 2G D Ex db eb op is IIC T4 Gb Ex tb op is IIIC T106 C Db 55 C Ta 85 C TR CU EAC 1Ex d e IIC T5 Gb X Ex tb IIIC T96 C Db X 55 C Ta 75 C Or 1Ex d e IIC T4 Gb X Ex tb IIIC T106 C Db X A 4 2 Functional Approvals EN54 10 approved per VdS FM approved per FM3260 A 5 Mechanical Specifications A 5 1 Enclosure Stainless Steel 316 Or Aluminum heavy duty copper free less than 1 red epoxy en...

Page 58: ...ye 40 40R is designed to withstand harsh environmental conditions A 6 1 High Temperature Designed to meet MIL STD 810C Method 501 1 Procedure II Operating temperature 167 F 75 C Storage temperature 185 F 85 C A 6 2 Low Temperature Designed to meet MIL STD 810C Method 502 1 Procedure I Operating temperature 57 F 50 C Storage temperature 65 F 55 C A 6 3 Humidity Designed to meet MIL STD 810C Method ...

Page 59: ... EMC Table 21 Electromagnetic Compatibility EMC Test Standard Level Per Electrostatic Discharge ESD IEC 61000 4 2 EN 50130 4 Radiated EM Field IEC 61000 4 3 EN 50130 4 Electrical Fast Transients IEC 61000 4 4 EN 50130 4 Surge IEC 61000 4 5 EN 50130 4 Conducted Disturbances IEC 61000 4 6 EN 50130 4 Power Frequency Magnetic Field IEC 61000 4 8 EN 50130 4 Radiated Emission IEC 61000 6 3 EN 55022 Cond...

Page 60: ......

Page 61: ...18 0 81 0 96 0 67 2 20 16 1 22 1 43 0 43 1 40 14 1 94 2 28 0 27 0 88 Use Table 23 to select wire gauge for power supply wires DO NOT connect any circuit or load to detectors supply inputs Select number of detectors connected in 1 circuit Select wiring length per your installation requirements Refer to power supply range for voltage extreme applied Table 23 Wiring Length in Feet Meters Number of De...

Page 62: ... N Number of detectors per loop R Resistance of wire per 100m see Table 22 V Voltage drop on the wire Calculate the voltage drop on the wire as follows V 2L x R x N x 0 2A 100 20 V Minimum required voltage of the power supply 0 2A is the maximum power consumption of the detector For example if N 1 1 detector in loop L 1000m Wire size 1 5mm see Table 23 the resistance per 100m for 1 5mm is 1 4Ω Cal...

Page 63: ...tions Wiring Option Detector Model Terminals 5 8 9 1 40 40R 1XXXX Fault Relay N C 0 20mA Sink 0 20mA Sink 2 40 40R 2XXXX Fault Relay N C Alarm Relay N C 0 20mA Source 3 40 40R 3XXXX Fault Relay N O Alarm Relay N C 0 20mA Source 4 40 40R 4XXXX Fault Relay N C Auxiliary Relay N O Auxiliary Relay N O 5 40 40R 5XXXX Fault Relay N O Auxiliary Relay N O Auxiliary Relay N O ...

Page 64: ...Wiring Instructions 64 SharpEye Single IR Flame Detector User Guide Figure 8 Typical Wiring for 4 Wire Controllers Using Option 1 or 2 Wiring Figure 9 0 20mA Wiring Option 1 Sink 4 Wire Default ...

Page 65: ...Wiring Instructions Figure 10 0 20mA Wiring Option 1 Converted to Source 3 Wire Figure 11 0 20mA Wiring Option 1 Non isolated Sink 3 Wire ...

Page 66: ...g Instructions 66 SharpEye Single IR Flame Detector User Guide Figure 12 0 20mA Wiring Option 2 and 3 Source 3 Wire available with the HART Protocol Note There are no 0 20mA outputs in wiring options 4 and 5 ...

Page 67: ...s in an addressable system with 4 wires only 2 for power and 2 for communication Using repeaters the number of detectors can be much larger 32 detectors for each repeater up to 247 on the same 4 wires When using the RS 485 network it is possible to read each detector status FAULT WARNING and ALARM and to initiate a BIT for each detector individually For more details contact SPECTREX Figure 13 RS 4...

Page 68: ......

Page 69: ... Simulator includes a halogen lamp that emits UV and IR radiation This energy is accumulated by a reflector directed towards the detector This allows the detectors to be tested under simulated fire conditions without the associated risks of an open flame Figure 14 Flame Simulator FS 1300 D 1 1 Ordering Information The P N of the Flame Simulator Kit is 380114 1 The kit is supplied in a carry case t...

Page 70: ... fire condition and may activate the extinguishing system or other alarms If activation is not desired disconnect inhibit them before the test and reconnect after the simulation To simulate a fire Verify you are at the correct distance from the detector according to the type of detector and the detector sensitivity Using the mechanical sight aim the flame simulator toward the center of the detecto...

Page 71: ...ep the flame simulator in a safe place when not in use D 1 5 Charging the Battery The flame simulator uses lithium ion batteries as a rechargeable power source When the batteries are fully charged the simulator operates at least 1 000 times without having to be recharged The simulator will not operate when the voltage from the batteries is lower than the required operational level 1 Simulator 3 Lo...

Page 72: ...ew on the locking disc Item 3 Screw on the back cover Item 4 Lock the back cover with the locking screw D 1 6 Battery Replacement To replace the battery Note The item numbers shown in this procedure can all be found in Figure 15 Place the flame simulator on a table in a safe area not exceeding 104 F 40 C Release the locking screw Unscrew the battery back cover Item 4 counterclockwise Unscrew the l...

Page 73: ... 10 50Hz D 2 2 Electrical Power 14 8V 4 X 3 7V rechargeable lithium ion battery Max Current 4A Battery Capacity 2 2AH Charging Time 2A at 2hr D 2 3 Physical Dimensions 230 x 185 x 136 mm Weight 5 5lb 2 5kg Enclosure aluminum heavy duty copper free black zinc coating Explosion proof enclosure ATEX IECEx Ex II 2 G D Ex d ib op is IIB H2 T5 Gb 20 C to 50 C 4 F to 122 F ...

Page 74: ...kV 8kV contact air Radiated Electromagnetic Field IEC 61000 4 3 20V m 80MHz 1GHz 10V m 1 4 2GHz 3V m 2 0 2 7GHz Conducted Disturbances IEC 61000 4 6 10Vrms 150kHz 80MHz Immunity to Main Supply Voltage Variations MIL STD 1275B Table 27 Emission Tests Emission Tests Title Basic Standard Level to be Tested Class Radiated Emission IEC 61000 6 3 40dbuv m 30 230MHz 47dbuv m 230MHz 1GHz Like Class B of E...

Page 75: ...Accessories D 3 Tilt Mount The tilt mount P N 40 40 001 provides accurate directional selection for optimum area coverage Figure 16 Tilt Mount ...

Page 76: ...here high temperatures exist or where the detector cannot be installed inside the area It comprises a special duct mount arrangement with a specific optical window to allow installation in high temperature duct applications The duct mount limits the cone of vision of the installed detector to 65 horizontal and 65 vertical The temperature allowed for the duct mount to be installed is 55 C to 200 C ...

Page 77: ...Accessories D 5 Weather Cover The weather cover P N 777163 protects the detector from different weather conditions such as snow and rain Figure 18 Weather Cover ...

Page 78: ...ently in order to clean its optical window The special air shield developed for SharpEye 40 40 series optical flame detectors allows their installation under environmental conditions where they may be exposed to oil vapors sand dust and other particulate matter The temperature of the air supply to the air shield should not exceed 60 C 140 F at any time Air pressure source Clean dry and oil free ai...

Page 79: ...r every 365 days HFT 0 PFD 3 2 x 10 4 3 2 of SIL 2 if only alarm relay is used for alerting PFD 3 7 x 10 4 3 6 of SIL 2 if 0 20mA interface is used to signal current as alarm SFF 95 fulfills the conditions of EN 61508 for SIL2 E 1 2 Guidelines for Configuring Installing Operating and Service The alert conditions according to SIL 2 can be implemented by an Alert signal via 20mA current loop Or Aler...

Page 80: ...N C contact of alarm relay terminals Connected to fault relay terminals The relay contacts alarm and faulty relay must be protected with a fuse rated at 0 6 of the nominal specified relay contact current The maximum contact rating that is allowed per SIL 2 is 30VDC The contact of the alarm relay opens if there is a fire alarm During the forwarding and evaluation of the alarm the relay contact open...

Page 81: ...roof d terminal compartment The EOL resistor can be situated in the rear part which is Ex e or Ex d depending on the application When the resistor is assembled the rear part can be used as Ex d only To meet the allowed power consumption the total resistance should be higher than 1 5KΩ Figure 20 End of Line Resistor Assembly ...

Page 82: ......

Page 83: ......

Page 84: ...Technical Support For technical assistance or support contact 8200 Market Blvd Chanhassen MN 55317 USA Phone 1 973 239 8398 Email spectrex spectrex net Website spectrex csc rmtna emerson com ...

Reviews: