TM 40/40M, Rev (14) February 2017
Mechanical Specifications
63
A.4
Approvals
Hazardous Area
Approvals
FM, CSA
Class I Div. 1 Groups B, C, and D;
Class II/III Div. 1 Groups E, F, and G
ATEX, IECEx
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96°C Db
(
–55°C ≤ Ta ≤ +75°C)
or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db
(
–55°C ≤ Ta ≤ +85°C)
TR CU / EAC
1Ex d e IIC T5 Gb X
Ex tb IIIC T96
°
C Db X
–
55
°
C
≤
Ta
≤
+75
°
C
or
1Ex d e IIC T4 Gb X
Ex tb IIIC T106
°
C Db X
–
55
°
C
≤
Ta
≤
+85
°
C
Functional
Approvals
EN54-10 approved by VdS
FM approved per FM3260
A.5
Mechanical Specifications
Enclosure
Stainless Steel 316
or
Aluminum, heavy duty copper free (less than
1%), red epoxy enamel finish
Water and Dust
Tight
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
Electronic
Modules
Conformal coated
Electrical
Connection
(2 entries)
¾
”
- 14NPT conduit
or
M25 x 1.5
Dimensions
4
”
x 4.6
”
x 6.18
”
/ 101.6 x 117 x 157 mm
Weight
Stainless Steel: 6.1lb/2.8kg
Aluminum: 2.8lb/1.3kg