Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
28
Performance Considerations
1.5.5 Output Signals
Outputs are available according to the default configuration or the wiring
options selected for the 40/40M detector. Determine the outputs for your
model according to Table 7.
The detector incorporates several types of output suitable to different
control systems:
0
–
20mA (stepped) with HART
Relays (alarm, fault, auxiliary)
RS-485 Modbus
Table 7: Available Output Types
Output Type
Version
Detector Status
Alarm Relay
40/40M
–
Options
1XXXX, 4XXXX, and
5XXXX
The relay is N.O.
40/40M
–
Options 2XXXX
and 3XXXX
The relay is N.O. and N.C.
Auxiliary Relay 40/40M
–
Options 4XXXX
and 5XXXX
The relay is N.O.
Fault Relay
40/40M
–
Options
1XXXX, 2XXXX, and
4XXXX
The relay is N.C. energized
40/40M
–
Options 3XXXX
and 5XXXX
The relay is N.O. energized
0
–
20mA
Current Output
40/40M
–
Option 1XXXX
Sink with the HART protocol,
(can be changed to Source
–
see Figure 11, Figure 12, and
40/40M
–
Options 2XXXX
and 3XXXX
Source with the HART
protocol
RS-485
All versions
Modbus protocol