TM 40/40M, Rev (14) February 2017
Configuring Your Detector
47
2.8.4 Function Setup
You can select the desired functions as detailed in Table 17.
Table 17: Functions
Function
Setting
Alarm Latch
Yes: Enable alarm latching.
No: Disable alarm latching (default).
Auxiliary Relay*
Yes: Activate auxiliary relay at warning level.
No: Activate auxiliary relay at alarm level
(default).
Automatic BIT
Yes: Perform automatic and manual BIT
(default).
No: Perform manual BIT only.
Alarm BIT
Yes: Successful manual BIT activates the alarm
relay for approximately 3 seconds (default).
No: Successful manual BIT does not activate the
alarm relay.
Auxiliary BIT*
Yes: Successful manual BIT activates the
auxiliary relay for approximately 3 seconds
(default).
No: Successful manual BIT does not activate the
auxiliary relay.
EOL*
Yes: Auxiliary relay is used as End of Line.
No: Auxiliary relay operates in accordance with
Functions 2 and 5 (default).
Note
: * Only available in Models 40/40M-4XXXX and 5XXXX
2.8.5 Heated Optics
The heated optics can be defined as one of the following modes:
Heated Mode
Off: Not operated
On: Continuously
Auto: Per temperature change
In AUTO mode, the default Heat On setting is 41°F/5°C. Heating stops when
the temperature is 27°F/15°C above the start temperature.
You can define the start temperature below which the window will be
heated. The temperature can be defined between 32
–
86°F / 0
–
30°C.