TM 40/40I, Rev (14) February 2017
Troubleshooting
53
4.2
Troubleshooting
This section is a guide to correct problems which may happen during normal
operation.
Table 20: Troubleshooting Table
Problem
Cause
Corrective Action
LEDs Off
Fault Relay at N.O.
0
–
20mA at 0mA
No power to the
unit
Check that the correct power
is sent to the detector.
Check power polarity.
Check wiring in the detector.
Send the detector back for
repairs.
Yellow LED flashes
at 4Hz
Fault Relay at N.O.
0
–
20mA at 0mA
Fault Detector
Low Voltage
Faulty Detector
Check the voltage at the
detector; verify at least 24V
at the detector terminal.
Send the detector back for
repairs.
Yellow LED flashes
at 4Hz
Fault Relay at N.O.
0
–
20mA at 2mA
BIT Fault
Faulty Detector
Clean detector window.
Re-power the detector.
Replace the detector.
Red LED
constantly on
If no fire exists,
then detector
alarm latched
Perform a
Reset
.
Alarm Relay at On
0
–
20mA at 20mA
Alarm condition
Check cause of alarm.
If no alarm, re-power the
detector.
Send the detector back for
repairs.
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...