RS-485 Communications Network
TM 799200 Rev. (4), April 2017
71
B.1
RS-485 Communications Network
By using the RS-485 network capability of the SafEye Xenon 700S Detector
and additional software, it is possible to connect up to 32 detectors in an
addressable system with 4 wires only (2 for power and 2 for
communication). Using repeaters, the number of detectors can be much
larger (32 detectors for each repeater): up to 247 on the same 4 wires.
When using the RS-485 network, it is possible to read each detector status
(FAULT, WARNING, and ALARM) individually.
For more details, contact SPECTREX.
Figure 15: RS-485 Networking for Wiring Option 3