Wiring Option Configurations
70
SafEye
TM
Xenon 700S Gas Detector User Guide
Figure 13: 0–20mA Wiring (Source) For Wiring Options 1 and 3
Notes:
The detectors are factory set to isolated 0–20mA-sink version.
For non-isolated 0–20mA version (source), connect Terminal 8 to
Terminal 1. The 0–20mA meter is connected between Terminal 7 and
Terminal 2.
Figure 14: 0–20mA 3 Wire Connection for Options 1 and 3