Zero Calibration
TM 799200 Rev. (4), April 2017
59
To perform the zero calibration procedure:
1
Switch from normal to alignment mode indication.
2
Switch from alignment to standby mode.
3
Switch from standby to zero calibration mode.
The 0–20mA output should now be at 1mA.
4
Wait up to 60 seconds until the mode switches to normal. The
detector reading is now set to normal and the 0–20mA output
indicates 4mA.
Use the Host HART (refer to
Manual TM888030
), RS-485 (refer to
Manuals TM888050
or
TM799060
), or move the magnetic mode
selector above the magnetic switch (see Figure 8) to switch between
each mode.
Figure 8: Magnetic Mode Selector