Operating Modes
TM888300 Rev. (Al), August 2019
29
The source statuses are listed in Table 3.
Table 3: Source LED Indications
Source
Status
LED Color
LED Mode
Fault
Yellow
4Hz, flashing
Normal
Green
1Hz, flashing
4.3
Output Signals
The SafEye system provides the following outputs:
•
•
4.3.1
0
–20mA Current Output
The 0
–
20mA output provides the detector status measurement with a continuous
reading of exact gas concentration.
The 0
–
20mA output functions as current Sink, but it can be configured as Source
(see).
The maximum permitted load resistance for the 0
–
20mA output is 500
Ω.
Table 4: Standard (default) 0
–
20mA Current for the Gas Channel
Current Reading
Status and Description
0mA +0.2mA
Fault in 0
–
20mA loop
1mA ±0.2mA
Zero calibration (in progress), Fault 2
2mA ±0.2mA
Fault 1 (non-critical)
3mA ±0.2mA
Maintenance call
4mA ±0.2mA
No gas present
4
–
20mA
Continuous measuring of gas concentration at a
range between 0
–
500ppm.m or full scale
21mA
Concentration is over the range limit (more than
full-scale concentration)
4.3.2
RS-485 Interface
The detector has an RS-485 Modbus-compatible input/output that can send data
communication to a PC loaded with the appropriate host software, and receive
data or control commands from the PC.