63
8
Troubleshooting
Problem
Cause
Solution
LEDs are off and fault is
indicated at 0mA level
Power is not supplied to
the detector
Supply power to the
detector
Both LEDs are on at
yellow and fault is
indicated at 0mA level
Fault 2
Bring the detector unit for
service
Both LEDs are flashing at
yellow and fault is
indicated at 0mA level
Low voltage is supplied to
the detector
Check the voltage level
supplied to the detector
One LED is on at yellow
and 4
–
20mA indication
level is 2mA
Dirt has accumulated on
the detector window or on
the light source window
Clean the optical windows
(see
One unit at least has been
moved or tilted
Perform realignment (see
page 55)
Power is not supplied to
the light source
Supply power to the light
source
The optical open path
beam is blocked
Remove the obstruction
One unit at least has been
moved or tilted
Perform realignment (see
page 55)
Electrical problem at the
light source
Perform SIC in order to
measure signal intensity
Bring the light source to a
technician for service if it
is not flashing