Select a suitable location that meets the following requirements:
A dedicated room with
restricted access
Electrically grounded
and
mechanically stable rack
, with
physical clearance
for unrestricted air flow and servicing: approx. 650 mm [25”] in front of rack, 770
mm [30”] in the back of rack
Clean,
dust-free
, and
stable
1
ambient temperature
not to exceed 35°C [95°F].
Virtually free of
EMC noise
Access to a reliable
grounded power outlet
Sufficiently dimensioned
power supply circuitry
, to prevent overloading of cir-
cuits.
The use of a regulating
UPS
(Uninterruptible Power Supply) is recommended.
Next Steps:
before
familiarizing yourself with the procedure for the
"Rack Installation" on the next
2.3
Rack Mounting: SAFETY
.
Before installing VelaSync in the fully extended rails, or before extending the unit
from the rack, ensure that the rack is stable enough to support the weight of the
fully extended unit. If you are using a standalone rack, it may be necessary to
install stabilizers to the rack.
Always extend only one unit at a time.
Install heavier servers near the bottom of the rack.
The unit weighs approximately 24 lbs (11 kg). Depending on your chosen install-
ation location, it may be advisable to lift the unit with two persons.
1
An environment where a constant temperature can be maintained during operation, to allow for the best pos-
sible timing accuracy.
2.3 Rack Mounting: SAFETY
CHAPTER
2
•
VelaSync User's Manual Rev. 3
25
Summary of Contents for VelaSync 1225
Page 2: ......
Page 4: ...Blank page II VelaSync User s Manual...
Page 12: ...BLANK PAGE X VelaSync User s Manual TABLE OF CONTENTS...
Page 28: ...16 CHAPTER 1 VelaSync User s Manual Rev 3 1 7 The VelaSync Web UI...
Page 34: ...BLANK PAGE 1 9 Regulatory Compliance 22 CHAPTER 1 VelaSync User s Manual Rev 3...
Page 104: ...BLANK PAGE 2 11 Configuring PTP 92 CHAPTER 2 VelaSync User s Manual Rev 3...
Page 251: ...Server management System specifications VelaSync User s Manual 239 APPENDIX...
Page 267: ...VelaSync User s Manual 255 APPENDIX...