Servicing Power Supplies
The server has redundant hot-serviceable power supplies. You can remove and replace a power
supply without shutting the server down, provided that the other power supply is online and
working.
For information about power configuration policies, refer to the Oracle ILOM documentation.
These topics describe how to service power supply modules.
■
“Locate a Faulty Power Supply” on page 87
■
“Remove a Power Supply” on page 88
■
“Install a Power Supply” on page 89
■
“Verify a Power Supply” on page 91
Related Information
■
“Rear Panel Components” on page 19
Locate a Faulty Power Supply
View the following LEDs, which are lit when a power supply fault is detected.
■
Rear PS Fault LED on the front bezel of the server. See
■
Service Required LED on the faulted power supply. See
Note -
The front and rear panel Service Required LEDs are also lit when the server detects a
“Front Panel Controls and LEDs” on page 34
Related Information
■
“Front Panel Components with Eight Drives” on page 11
Servicing Power Supplies
87
Summary of Contents for S7-2L
Page 1: ...SPARC S7 2L Server Service Manual Part No E73201 04 March 2017...
Page 2: ......
Page 10: ...10 SPARC S7 2L Server Service Manual March 2017...
Page 26: ...26 SPARC S7 2L Server Service Manual March 2017...
Page 44: ...44 SPARC S7 2L Server Service Manual March 2017...
Page 61: ...Remove the Fan Cover Use a T6 Torx screwdriver Preparing for Service 61...
Page 64: ...64 SPARC S7 2L Server Service Manual March 2017...
Page 76: ...76 SPARC S7 2L Server Service Manual March 2017...
Page 86: ...86 SPARC S7 2L Server Service Manual March 2017...
Page 156: ...156 SPARC S7 2L Server Service Manual March 2017...