Page 2 of
20
INSTALLATION , SERVICING & OPERATING INSTRUCTIONS
1.
TECHNICAL DATA
Table 1
MODEL
Ultra 7-N
Ultra 7-L
Heat Input Qn
6.66 kW (Hs) 6.0 kW (Hi)
Appliance Type
A
1
Appliance Cat.
I
2H
I
3P
Adjusted for
2H G20 20 mbar
3P G31 50 mbar
Setting Pressure
19.0 mbar
50.0 mbar
Injector
2 x Ø1.30 mm
2 x Ø0.09 mm
Orifice Plate
None
None
Electrical Supply
230v~50Hz 25W
Fuse Externally
3A
Gas Connection
Rc - ½
Dimensions
L = 0.48m W = 0.58m H = 0.35
Weight
14 Kg
Table 2
MODEL
Ultra 14-N
Ultra 14-L
Heat Input Qn
13.33 kW (Hs) 12.0 kW (Hi)
Appliance Type
A
1
Appliance Cat.
I
2H
I
3P
Adjusted for
2H G20 20 mbar
3P G31 50 mbar
Setting Pressure
18.8 mbar
50.0 mbar
Injector
2 x Ø1.85mm
2 x Ø1.20mm
Orifice Plate
Ø38mm
Ø40mm
Electrical Supply
230v~50Hz 25W
Fuse Externally
3A
Gas Connection
Rc - ½
Dimensions
L = 0.85m W = 0.58m H = 0.35m
Weight
22 Kg
Table 3
MODEL
Ultra 21-N
Ultra 21-L
Heat Input Qn
19.98 kW (Hs) 18.0 kW (Hi)
Appliance Type
A
1
Appliance Cat.
I
2H
I
3P
Adjusted for
2H G30 20 mbar
3P G31 50 mbar
Setting Pressure
18.7 mbar
50.0 mbar
Injector
2 x Ø2.25mm
2 x Ø1.45mm
Orifice Plate
Ø44mm
Ø42mm
Electrical Supply
230v~50Hz 25W
Fuse Externally
3A
Gas Connection
Rc - ½
Dimensions
L = 1.22m W = 0.58m H = 0.35m
Weight
30 Kg