Form #43219000
May 2021
NOTE:
The clearance to combustible materials noted above must be maintained at all times and the
same clearance distances must be adhered to from any other materials that may be damaged by
temperatures 90
o
F above the ambient temperature.
It is the installer’s responsibility to ensure that
building materials with a low heat tolerance (such as plastic, vinyl siding, canvas, tri-ply etc.) which may
degrade at lower temperatures are protected to prevent degradation. Clearances to combustibles are
posted on the reflector near the control end of the heater.
Fire sprinkler heads must be located at an appropriate distance from the heater. This
distance may exceed the published clearance to combustibles. Certain applications will require the use of
high temperature sprinkler heads or relocation of the heaters.
Sprinkler systems containing propylene glycol or other flammable substances are not to be used in
conjunction with this heater without careful consideration for and avoidance of potential fire or explosion
hazards. For further information consult NFPA 13. Always observe applicable state and local codes.
5)
RSCA SPECIFICATIONS
COMPLETE MODEL
& SUFFIXES
GAS
TYPE
INPUT
BTU/HR
MINIMUM
MOUNTING HEIGHT
ORIFICE
SIZE
SHIPPING
WEIGHT
RSCA3-N1, N1B
Natural
26,000
12 ft.
#42 (0.0935)
30 lbs.
RSCA3-L1, L1B
Propane
26,000
12 ft.
#53 (0.0595)
30 lbs.
RSCA6-N1A, N1B
Natural
52,000
14 ft.
#32 (0.1160)
40 lbs.
RSCA6-L1, L1B
Propane
52,000
14 ft.
2 mm (.0787)
40 lbs.
RSCA3-N5B, N5C
Natural
26,000
12 ft.
#42 (0.0935)
30 lbs.
RSCA3-L5B, L5C
Propane
26,000
12 ft.
#53 (0.0595)
30 lbs.
RSCA6-N5B, N5C
Natural
52,000
14 ft.
#32 (0.1160)
40 lbs.
RSCA6-L5B, L5C
Propane
52,000
14 ft.
2 mm (.0787)
40 lbs.
RSCA10-N5B, N5C
Natural
104,000
15 ft.
#32 (0.1160)
70 lbs.
RSCA10-L5B, L5C
Propane
104,000
15 ft.
2 mm (.0787)
70 lbs.
MODEL SUFFIXES:
REFLECTOR TYPE:
GAS-PIPE
CONNECTION:
Gas Type:
Ignition System:
N
= Natural
L
= Propane
1
= Standing Pilot (Millivolt)
5 = Direct Spark (120V/.40A/60Hz)
Standard or
Optional Parabolic Reflector Extension
1/2" NPT (Female)
*MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and uniform energy
distribution for complete building heating applications. Consult your Space-Ray representative for the particulars of your
installation requirements.
6
INSTALLER
In locations used for storage of combustible materials where they may be stacked below the heater,
NFPA 54 requires that the installer must post signs that will “specify the maximum permissible
stacking height to maintain the required clearances from the heater to combustibles.” Space
-Ray
recommends posting these signs adjacent to the heater thermostat or other suitable location that will
provide enhanced visibility. It is important to provide warnings to alert individuals of potential hazards
and safety actions. Posted signs should state the hazards for the particular application and be legible
to building occupants.