background image

 

Form 44201129 

Oct 2019 rev A

  

13 

A.

 

Combustion Air Adjustment (System Hot) 

 

It is IMPORTANT to finally adjust the amount of combustion air to each burner in the system when the system 
is operating at thermal equilibrium. 
 

1.

 

Operate the system for 20 minutes to attain thermal equilibrium then adjust the amount of combustion air at 
each burner by carrying out the procedures at 2 to 4 on each appliance in turn. 
 

2.

 

Connect a suitable manometer (0.01mbar resolution) to the test nipple protruding from the rear panel of the 
Control Box (adjacent to the Air Inlet Adaptor) as outlined in the separate installation and operation 
instructions supplied with the heater. 
 

3.

 

Reposition the adjustable gate of the appliance damper (after unscrewing the clamp screw) to attain a 
negative pressure reading on the manometer of 0.65mbar ± 0.05mbar. Secure the adjustable gate in 
position with the clamp screw. 
 

4.

 

Finally check all the test points again to verify that the negative pressure at each of the burners is 0.65mbar 
± 0.05mbar. 

 
 

11.0)

 

 SERVICING 

 

It is essential that at least once a year, preferably before the heating season, a qualified person service the 
appliance.  In exceptionally dirty conditions, such as may occur in a foundry, more frequent servicing may be 
desirable. 

 
 

IMPORTANT: 

  

A.    Do not rest anything, especially ladders, against the appliance. 
B.

 

Gas and Electricity supplies must be isolated before commencing servicing work or replacement of 
components. 

C.

 

Unless instructed to the contrary, re-assemble components in reverse order. 

D.

 

Check all joints for gas soundness after carrying out any servicing of the appliance. 

E.

 

On completion of a service/fault finding task which has required the breaking and remaking of electrical 
corrections, the following checks, using a multi-meter must be made. 

 

o

 

Earth continuity check 

o

 

Polarity check 

o

 

Resistance to earth check 

 

1.

 

Exhaust Fan 

 

 

 

Inspect the main impellor and secondary cooling impellor and remove any dust by brushing with a soft brush. 
Remove any dust from the guard covering the secondary cooling impellor. Check that the impeller rotates freely 
and that there is no excessive play in the bearings.  The bearings are pre-lubricated and require no attention. 

 

2.

 

Flue Pipes/Manifold 

 

 

It is important that periodic sweeping of the flue is carried out according to the  National or Local regulations in 
force. 

 

3.

 

Re-assemble and Commission 

 

 

Re-assemble the appliance in reverse order and commission in accordance with the instructions  contained in 
Section 10.0. 

 

4. 

Auxiliary Controls

 

 

 

Room thermostats, time switches, frost thermostats etc should be checked to ensure correct functioning, and are 
set to the user requirements. 

 

Summary of Contents for ADL25-HB

Page 1: ...ICE INSTRUCTIONS ARE INCLUDED IN THE SEPARATE MANUALS SUPPLIED WITH EACH HEATER Models LRU25 HB LRU30 35 40 45 HB LRL25 HB LRL30 35 40 45 HB ADU25 HB ADU30 35 40 45 HB ADL25 HB ADL30 35 40 45 HB Gas F...

Page 2: ...tem Exhaust Manifold 4 5 0 Gas Supply 6 6 0 Electrical Supply 6 7 0 System Ventilation 8 7 1 Flue Size 9 8 0 Damper Assembly Attachment Linear Models 9 8 1 Damper Assembly Attachment U Tube Models 10...

Page 3: ...e that the burner is correct for the gas type in the building 3 0 GENERAL INFORMATION This heater is a self contained infrared radiant tube heater designed for use where flammable gases or vapors are...

Page 4: ...lity of exposure to volatile and low flash point materials exists it could result in property damage or death This heater must not be installed in a spray booth where the heater can operate during the...

Page 5: ...rm with the plan provided 2 For suspending the manifold it is recommended that suitable protected welded chain 3mm x 65links m stainless steel flexible wire or similar and manifold tube hangers be use...

Page 6: ...condensate trap 15mm PVC or galvanised not copper should be U shape with a minimum depth of 250mm and with the outlet connected to a drain Fan Type 1 Fig 5 4 For fan type 3 Part No 4262254 which are...

Page 7: ...to national or Local Regulations to connect the appliance to the gas supply Minimum size to be 12 7mm bore 3 LPG G30 G31 at 29 37mbar nominal supply pressure appliance cat 3 Maximum supply pressure Pm...

Page 8: ...atively connection may be made via a fused 3 pin plug and un switched shuttered socket both complying with the requirements of National or Local Regulations Neither thermostat nor switch are supplied...

Page 9: ...elow the level of the heater s Up to and including 60kW 4 5cm2 kW Over 60kW 270cm2 2 25cm2 kW in excess of 60kW total rated heat input Where the air supply openings can be closed it shall only be poss...

Page 10: ...n the Control Box Air Inlet and any rigid ducting and be secured to the Air Inlet with hose clips The maximum length of ducting should be 15m with a maximum of two 900 bends Where outside combustion a...

Page 11: ...Coupling up to the stop and is positioned with the adjustable slide flange at its lower edge Tighten the nuts of the Torctite Coupling to secure the Damper Assembly to the Radiant Tube taking care to...

Page 12: ...holes 5 5mm through both the tube and fittings one hole to be at 12 o clock to prevent possible leakage of condensate and rivet the tube to the fittings 5 x 6 pop rivets Fig 11 10 0 COMMISSIONING Insp...

Page 13: ...hing on the electricity supply to the system control and setting the time switch and thermostat to demand heat Carry out the procedures at 5 and 6 on each of the appliances in the system 5 Connect a s...

Page 14: ...nt servicing may be desirable IMPORTANT A Do not rest anything especially ladders against the appliance B Gas and Electricity supplies must be isolated before commencing servicing work or replacement...

Page 15: ...fan F Type 3 Fan G Remove the cover from the Exhaust Fan terminal housing and remove the electrical leads H Disconnect the flue from the fan outlet I Slacking the Hose Clips securing the Fan Connecto...

Page 16: ...occurs switch off the electricity supply to the zone or system fan wait for 10 seconds before switching on the electricity supply to the zone or system fan to repeat the ignition sequence It is not po...

Page 17: ...Form 44201129 Oct 2019 rev A NOTES...

Reviews: