b.701Server software

(1)Tick Node ID

(2)Tick IP and key-in the new IP address you had changed by

      Net 727 Software.

 

c. Click “Hyper-Terminal”. Shown as follows:

d. Key-in any temporary name. It is not important 

     matter.

e. Choose which COM port that Converter 

     connect  and click  “ OK ” to exit. 

f. Set Port Settings to 9600, 8, None, 1, None 

     and click  “OK” to save.

g. TCP/IP module already gets IP address now 

     shown as follows:

h. Please refer above         item and enter 

      item on the        so that set all parameters.

i. Note that enter item 6 on the        to save 

     parameter after finished setting up 

     parameter.

 j. Then switch DIP SW-1 and SW-2 

      to “OFF” position.

1

2

3

C.Software Operation

1.Set up communication port at 701Server software. 2.Node ID setting

a.Hardware

    Power Off → Take off the battery 

    connector from BAT+ socket → 

    Set up node number by 

    8 dip-switch → Plug in battery → 

    Re-apply the power

3.Get IP address by COM Port  

    At first, PCB diagram as follows and Connect a Converter (RS485 to RS232) to the HOST of the PCB:

1

2

3

4

Switch DIP SW-1 to “OFF” position.

Switch DIP SW-2 to “ON” position. 

(Serial Setup Mode)

Switch Jumper J3, J4 and J5 to 

RS-485 position.

Switch Jumper J2 to RS-485 

position.

a. Power on. 

b.To modify parameter on the TCP/IP module through the 

    Hyper-Terminal function of the Window.

    (Start → Programs → Accessories → 

    Communication → Hyper Terminal)

1

3

4

2

v070604

4

TCP/IP module Ver: 2.07

AR-716E