Operation cont.

Resistance Measurement

 

               Never test resistance

on a live circuit. 

WARNING:

Hz%

MODE

®

1. Set the rotary function switch to the

   

 

Ω

 

        

•))) CAP 

position.

2. Press the 

button until the 

“M

Ω

    symbol appears on the display.
3. Touch the test probe tips across the circuit

    or part under test. It is best to disconnect

    one side of the part under test so the rest

    of the circuit will not interfere with the

    resistance reading.
4. Read the resistance in on the LCD display.

MODE

Ω

Red               Black     Black           Red

 

Probe            Probe    Probe           Probe

 

Forward test   Reverse test  

 

1. Set the rotary function switch to the

   

 

Ω

 

        

•))) CAP 

position.

2. Press the 

button until the 

“      ”

    symbol appears on the display.
3. Touch the test probes to the diode under test.
4. Forward voltage will indicate 0.4V to 0.7V on

    the LCD display. Reverse voltage

    will indicate 

“OL”

. Shorted diodes

    will indicate near 0V and an open

    diode will indicate 

“OL”

 in both

    polarities.

MODE

Diode Test

    Never test diodes in a live circuit.

WARNING:  

Hz%

MODE

®

8

Operation cont.

Continuity Test

 

               Never test continuity

on a live circuit. 

WARNING: 

 

1. Set the rotary function switch to the

   

 

Ω

 

        

•))) CAP 

position.

2. Press the 

button until the 

“•)))”

    symbol appears on the display.
3. Touch the test lead probes to the device

    or wire being tested.
4. A tone will sound if the resistance is

   approximately 30 ohms or less. 

MODE

Capacitance Measurements

 

               Safely discharge capacitors

before taking capacitance measurements. 

WARNING:  

 

1. Set the rotary function switch to the

   

 

Ω

 

        

•))) CAP 

position.

2. Press the 

button until the 

“nF ”

    symbol appears on the display.
3. Connect the test leads to the capacitor

    to be measured.
4. Read the capacitance on the LCD display.

    It may take up to a minute to obtain a

    stable reading on large capacitors. 

MODE

Hz%

MODE

®

Hz%

MODE

®

Wire

Summary of Contents for 10020N

Page 1: ...l rights reserved southwiretools com 1 855 SW T00LS Toll Free Technical Help Línea de Ayuda Técnica Gratuita Scan for warranty information and to access our mobile site Escanea para informaciónde garantía y acceso a nuestro sitio móvil Operating Instructions 10020N 3in1 MULTIMETER Hz MODE TESTING EQUIPMENT E361819 Instrucciones de Operación MULTÍMETRO 10020N 3en1 ...

Page 2: ...lectrical storms V UV ZL OL TL LY ULHY L_WSVZP L NHZLZ K Z VY HWVY V UV ZL OL TL LY PM P VWLYH LZ PUJVYYLJ S Protection may be compromised V UV HWWS VS HNL VY J YYLU OH L_JLLKZ OL TL LY Z TH_PT T YH LK PUW SPTP Z 2 Input Limits Function Maximum Input Voltage AC Voltage DC Frequency Duty Cycle Amperage µA mA AC DC Resistance Diode Continuity Test 600V AC DC 600V AC DC Maximum Amperage 200mA Maximum...

Page 3: ...lity power and outdoor conductors Primary distribution panels Overhead or underground lines to detached buildings Incoming service entrance from utility Outdoor pumps WARNING Operation is limited to CAT II applications when the insulated tips are removed from one or both test probes Refer to Input Limits section of this manual for maximum voltage ratings CAT III 1000V CAT IV 600V CAT II 1000V Insu...

Page 4: ...cautions when working on live voltages Do not measure current on circuits that exceed 500 V WARNINGS Observe all safety precautions when working on live voltages WARNING Hz MODE V MODE 1 For current measurements up to 200mA AC DC set the rotary function switch to the mA position 2 For current measurements up to 4000µA AC DC set the rotary function switch to the µA position 3 Press the button to se...

Page 5: ...display Reverse voltage will indicate OL Shorted diodes will indicate near 0V and an open diode will indicate OL in both polarities MODE Diode Test Never test diodes in a live circuit WARNING Hz MODE 8 Operation cont Continuity Test Never test continuity on a live circuit WARNING 1 Set the rotary function switch to the Ω CAP position 2 Press the button until the symbol appears on the display 3 Tou...

Page 6: ...and other factors may effect operation Use other methods to verify live voltage if there is any uncertainty NOTE The detector is designed with high sensitivity Static electricity or other sources of energy may randomly trip the sensor This is normal operation Hz MODE Hz MODE Hz 10 REPLACING THE BATTERY To avoid electric shock disconnect test leads from any source of voltage before removing the bat...

Page 7: ...tion contamination modification improper maintenance or repair operation outside of specifications or abnormal handling of the product Southwire s sole liability and the purchaser s exclusive remedy for any breach of this warranty is expressly limited to Southwire s repair or replacement of the product Whether Southwire repairs or replaces the product will be a determination that Southwire makes a...

Reviews: