Electrical Connections 

 

Main Power to the Machine Connections 

The 3 phase 220 voltage (208 

 240 V acceptable) is connected to L1, L2 and L3 at the power switch inside the 

electrical box.  Connect the ground wire as shown in the figure 8.   

 

 

Figure 8 – Connect the Ground Wire

 

 

 

 

 

Machine Grounding 

It is strongly recommended that the machine be earth grounded. A dedicated copper rod 8 feet or so in length 
should be driven into the ground near the LPM. A ground wire should then be run from the filter ground to the 
copper rod. Please see Figure 9 for where to connect the ground wire on the filter. The ground wire should 
come up through the bottom of the electrical cabinet in the hole nearest the door. The wire should be 6 gage in 
size. Figure 10 shows an OK method for grounding.

 