MOUNT PHASES PER ENGINEERING DRAWINGS

3

6

PIERCE VERTICAL BEARING 

SET-SCREW COMPLETELY 

NOTE: 

This will be the 

only

 piercing 

until step 13. Ensure the full weight of the 

vertical pipe is supported by the vertical 

bearing and maintain the gap required 

between the coupling and gear operator. 

Then pierce collar. Also, confirm auxiliary 

arm assembly is correctly mounted per the 

operating mechanism drawing. 

INSTALL ADJUSTABLE ARM & 

DRIVE PHASE CLEVISES

Typical Mounting 

Bolt Locations 

Refer to operating mechanism drawing for pole orientation and mounting 

Vertical Bearing Set Screw 

(Pierce Bolt)

Drive Phase Clevis

Adjustable Arm

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

REVIEW BILL OF LADING (BOL) 

A.

 

Check the materials received against the packing list

B.

 

Report any shortages or damaged equipment to Southern States

2

REVIEW BILL OF MATERIAL (BOM)

A.

 

Inventory all parts against the BOM found on the op-mech sheet inside  

      the drawing package

B.

 

Report any missing or damaged parts to Southern States

TERMINOLOGY OVERVIEW

A

: Live Parts

B

: Insulator 

C

: Base

D:

 Jaw

E:

 Blade

F:

 Counterbalance

G:

 Contact Fingers

H:

 Switch Operating Arm

I:

 Bearing

J:

 Arcing Horns

A

B

C

C.

 

A typical shipment will include:

- 3 phase switch (base, insulators, & live parts)

- Operating mechanism box 

- Operating pipe

MOUNT VERTICAL BEARING, 

PIPE, & OPERATOR

4

1/4” 

to

 

3/8”

 

gap

Vertical Bearing Support

Vertical Pipe

Operator

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

5

7

CONNECT & TIGHTEN DRIVE PIPE BETWEEN 

ADJUSTABLE ARM & AUXILIARY ARM OF DRIVE 

PHASE WITH APPROPRIATE CLEVISES

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

NOTE:

 

DO NOT PIERCE UNTIL STEP 13

8

MATCH-MARK CLEVIS 

CONNECTIONS, ADJ. ARM, 

& OPERATOR COUPLING TO 

MONITOR SLIPPAGE

Refer To Instruction Book Section: 

Installation & Adjustment Procedures

Drive Pipe

D

E

F

G

H

I

J

Mounting Bolt 

Locations

Vertical 

Bearing 

Support

Special Handling Required 

-

 

A  qualified  rigger  and  lift  plan  are 

required due to possible off center, 

high, center of gravity. Lift by switch 

base only. 

WARNING

SLING ATTACHMENT

Publication No. QSG101-EV-2 R0 12172020

SECURE 

BLADE WITH 

TIES DURING 

LIFTING

Because the phase is top heavy, the 

base must be bolted to the structure 

before removing lifting straps to 

prevent tipping. 

CAUTION

Note

: All material is marked with JO number

Vertical Pipe