Page 23 of 26
Installation & Adjustment Procedures
3.1. Worm gear operator (SEGO – Safety Enhanced Gear Operator) (Optional)
3.1.1. The weight of the vertical operating pipe should be supported by pipe
collar by maintaining the 1/4”-3/8” gap.
3.1.2. When the switch is properly adjusted the operator handle should hang
freely in both the open and closed positions to permit the use of the
customer supplied padlock.
Figure 14: Type SEGO (Safety Enhanced Gear Operator)
2.3 Swing handle operator
2.2.1. When the switch is properly adjusted the handle should hang vertically and
free in both the open and closed positions to permit the use of a customer
supplied padlock.
3.3 Electrical motor operator
2.3.1. Please refer to motor operator instruction manual for proper installation and
setup.
2.3.2. Use manual operation while completing switch setup.
2.3.3.
Do not
electrically operate until all switch adjustments are complete.
ALWAYS
operate the motor operator decoupled first to ensure proper
setup.
Be aware that there is an adjustable stop on the operator.
Do not over operate as damage will occur to the
operator.