This section enables the operator to determine the cause of operation problems and
suggests remedies for the problems. If there are several likely causes, investigate the
simpler solutions first. If further assistance is required, contact your local distributor
or South-Tek Systems.
Symptoms
Probable Cause
Corrective Action
System Not
Powering On
Too Low or Too High
Voltage/Amperage
Check Electrical Source
Circuit breaker tripped
Reset circuit breaker
Fuse Blown
Replace fuse on electrical panel
System is OFF (Selector switch on
Home screen is in the OFF position)
Touch the switch to turn it to the ON position
Defective Wiring
Check all wired connections
Purity Status
Remains
Red/Alarming
Too little or no flow to Quick-Check
Check APS flow settings and ball valve position
Leak within system
Check for leaks
Exhaust port plugged
Check that exhaust tube is not blocked
O2 analyzer malfunction
Replace O2 analyzer
Flow Status Remains
Alarming
Too little or no flow to Quick-Check
Check APS flow settings and ball valve position
Valves, lines, or clear flow indicator
before the analyzer is blocked up
Check if system is blocked up
Lines are not connected/broken
coming from the AutoPurge System
Replace or reconnect lines
Valves are not actuating
Check solenoid valve wires/replace valves