- 37 -
SORHEA
G-FENCE
5) Repeat steps 2) and 3) for the second cable.
6)
Turn switch to “DETECT”.
The buzzer will emit 2 short beeps to confirm entry into detection mode.
7) Trigger alarms on the fence to test the alarm triggering on cable 1 and 2. The red LED is lit
and the buzzer beeps when there is an alarm.
Wait 10 seconds between 2 alarm triggering.
8) Repeat steps 1) to 6) for the next Control Unit (UG).
Please check that all Control Units (UG) have different address.
(See chapter §4.1 Wiring of the Control Unit (UG))
9) Reconfigure the Link Unit (UR), situated between the two configured Control Units (UG), in
“
UR
” mode.
10) Close the cover of the Link Unit (UR).
UR
1
st
configured UG
2
nd
configured UG
Cable 1
Cable 2
Cable 1
Cable 2
UT/UR