Troubleshooting

Symptom

Probable Cause

Float in actuated position but no output 
signal.

 No power supply.

 Switch damaged. (Replace.)

Float in de-actuated position but still 
receiving an output signal. 

 Switch damaged. (Replace.)

Control will not function when installed 
but operates when removed from pro-
cess connection.

 Inadequate float travel. Float travel 

restricted by mounting nozzle. See 
Mounting Requirements.

Liquid in vessel at the actuation level 
but unit does not respond.

 Leaky or collapsed float. (Replace.)

 Liquid specific gravity too low.

 Float stem bound up or dirty. (Clean.)

Part Number

Description

3130-052

316SS Float Assembly

3130-106

W9 - SPST Hermetically Sealed Switch Capsule

3130-245

W1 - SPDT Hermetically Sealed Switch Capsule

3130-259

W1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)

3130-107

L9 - SPST Hermetically Sealed Switch Capsule

3130-244

L1 - SPDT Hermetically Sealed Switch Capsule

3130-260

L1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)

9227-028

MC Manual Check Assembly for 1 1/2” NPT Body*

9227-029

MD Manual Check Assembly for 1 1/2” NPT Body*

9227-024

MC Manual Check Assembly for 2” NPT Body*

9227-025

MD Manual Check Assembly for 2” NPT Body*

3130-040

20’ Remote Cable with two cable crimps, for use with MC or MD 
accessory only.

Replacement Parts

* Unit must have originally been supplied with MC or MD option.

Summary of Contents for 1510

Page 1: ...meplate instructions shown here NOTE If you suspect that a product is defective contact the factory or the SOR Representative in your area for a return authorization number RMA This product should only be installed by trained and competent personnel 1510 Side Mounted Level Switch General Instructions NC indicates circuit is closed Registered Quality System to ISO 9001 Design and specifications are...

Page 2: ...andle for actuation at the desired length The unit may be mounted in any of the following installation arrangements 1 1 2 NPT half coupling No full coupling 2 NPT full coupling Use in conjunction with 2 x 1 1 2 NPT bushing as required 2 NPT pipe tee Use in conjunction with 2 x 1 1 2 NPT bushing as required Optional flanged mounting Optional chamber mounting Linear mm inches Drawing 0098636 REMOTE ...

Page 3: ...he shaft Float Attachment Series 1500 with Flange Safety Integrity Level SIL Installation Requirements The SOR pressure switches have been evaluated as Type A safety related hardware To meet the necessary installation requirements for the SIL system the following information must be utilized Proof Test Interval shall be one year Units may only be installed for use in Low Demand Mode Products have ...

Page 4: ... model number Linear mm inches Drawing 0390760 177 8 7 00 55 6 2 19 14 3 0 56 79 0 REF 3 11 31 5 1 24 MAX 53 8 2 12 FLOAT TRAVEL 22 2 WRENCH FLATS 0 87 FLOAT 1 1 2 NPTM PROCESS CONNECTION OR FLANGE MOUNTING NOT SHOWN BODY 1 2 NPTF ELECTRICAL CONNECTION WIRE LEADS 457 2 18 00 MIN LENGTH COLOR CODED AND MARKED 44 5 WRENCH FLATS 1 75 1 NOTES 1 ACTUATE DEACTUATE POINTS VARY OPERATES 56 4 SATISFACTORIL...

Page 5: ...e permanently attached leads must be suitably protected against mechanical damage and terminated in a suitable junction box or terminal facility Ensure that the wiring conforms to all applicable local and national electrical codes and install unit s according to relevant national and local safety codes Electrical connection is free wire leads with a 1 2 NPT F conduit connection Use two wrenches on...

Page 6: ... 1 2007 04 IEC 60079 11 2011 IEC 60079 25 2010 02 IEC 60079 0 2004 IEC 60079 11 1999 ATEX Listing Information Drawing 0720554 Manufacturer s Registered Trademark Product Type Identification Product Model Identification For Type 1510 Level Switches equipped with DPDT relays a wiring schematic and pin position schematic is shown below When the 1510 is actuated the coil will energize and make both NO...

Page 7: ...ectric Switches SOR Inc 14685 West 105th Street Lenexa Kansas 66215 2003 5NITED 3TATES OF MERICA December 18 2017 4 8 IRECTIVE 5 QUIPMENT NTENDED FOR USE IN 0OTENTIALLY XPLOSIVE TMOSPHERES 4 8 ARKING X ARKING II 1 G Ex ia IIC Ga Ex ia IIC Ga 4 d 4A d OR 4 d 4A d OR 4 4A 4 4A II 2 G Ex db IIC Ga Gb Ex db IIC Ga Gb 4 d 4A d OR 4 d 4A d OR 4 4A 4 4A EC Type Examination Certificate Baseefa06ATEX0271X I...

Page 8: ... float Replace Liquid specific gravity too low Float stem bound up or dirty Clean Part Number Description 3130 052 316SS Float Assembly 3130 106 W9 SPST Hermetically Sealed Switch Capsule 3130 245 W1 SPDT Hermetically Sealed Switch Capsule 3130 259 W1 SPDT Switch Conduit Connection Assembly CK Option Only 3130 107 L9 SPST Hermetically Sealed Switch Capsule 3130 244 L1 SPDT Hermetically Sealed Swit...

Reviews: