Sontay WD-AMX Manual Download Page 2

Page 2 of 5

WD-AMX

Date of Issue: 17/08/2012

Issue Number: 5.4

Supply Voltage: 

WD-AMX-1 

24Vac/dc 

±10%

WD-AMX-2 

230Vac @ 50Hz 

Supply current 

50mA max. 

Output   

12A @ 250Vac 

LED Status indication for: 

Error 

condition

Input 

sensitivity

Relay output mode 
Learning 

Mode

Response time 

 

<1 sec. after exposure 

Max. sensor cable length   200m (656ft) with leader cable 
Alarm hysteresis   

Dependent on sensitivity 

Audible alarm output 

[email protected] @ 10cm  

Electrical  

Terminals for 0.5-2.5² cable 

Connections

Rising 

cage 

Ambient: 

Temperature 

0°C to 40°C (32 to 104°F) 

RH

0-80% 

non-condensing

Dimensions 

72 x 64 x 55mm 
(2.83 x 2.52 x 2.17”) 

Weights: 

WD-AMX-1 

100g 

(0.22lb)

WD-AMX-2 

240g 

(0.53lb)

Country of origin   

UK 

The products referred to in this data sheet meet the 
requirements of EU 2004/108/EC and 2006/95/EC 

WD-AMX-1 

24Vac/dc water detection alarm module with 
audible  alarm and LED status indication 

WD-AMX-2 

230Vac water detection alarm module with 
audible  alarm and LED status indication 

 Warning! 

When installed, the output relay contacts may carry 
240Vac. Special care must be taken to isolate the switched 
voltages prior to any work being undertaken. 

Specification: 

Part 

Codes: 

Reviews: