Sontay SD-521 Quick Manual Download Page 3

Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or 

expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice. 

 

Page 3 of 3 

UK Sales Tel: 0845 345 7253 

International Tel: +44 1732 861225 

For the latest information and product updates, register at www.sontay.com 

SD-521 

Issue: 5.8 

Date Of Issue: 02/06/2010 

© 2010 Sontay Limited. All rights reserved. 

Installation 

1.  The SD-521 should only be installed by a competent, 

suitably trained technician, experienced in installation 
with hazardous voltages. (>50Vac & <1000Vac or 
>75Vdc & 1500Vdc)  

 

 

 

 

 

2.  Ensure that all power is disconnected before carrying out 

any work on the SD-521.   

 

 

 

 

3.  Maximum cable is 2.5mm², care must be taken not to 

over tighten terminals. 

 

 

 

 

 

4.  If  the sensor is mounted outside, it is recommended 

that the unit be mounted with the cable entry at the 
bottom. If the cable is fed from above then into the 
cable gland at the bottom, it is recommended that a rain 
loop be placed in the cable before entry into the sensor.
 

 

5.  Drill two holes at 142mm centres, and a 26mm dia. 

probe hole as dimensions on page 3. Fix the IP65 hous-
ing to the duct with appropriate screws. 

 

 

 

6.  Remove the front cover by undoing the two screws on  

the lid and separating from the main body.   
 

 

7.  Feed the cable through the waterproof gland and termi-

nate the cores at the terminal block. Leaving some slack 
inside the unit, tighten the cable gland onto the cable to 
ensure water tightness. 

 

 

 

 

 

8.  Replace the lid after the connections have been made.

 

 

 

 

 

 

 

 

9.  Ensure the voltage is within the specified tolerances.

 

 

 

 

 

 

 

 

10. Allow 3 minutes before checking functionality. 

 

 

11.

Allow 30 minutes before any pre-commissioning checks.

 

 

Connections 

 
Links & adjustments:   

Terminals: 

 
VR1 Do 

NOT adjust   

1 - 0V   

              

VR2 

Sensitivity 

 

2 - 24Vac/dc 

LK1: 

 

 

 

3 - 2-10Vdc Output 

ON = Output damped   

4- Relay common 

OFF = Output un-damped 

5 - Not used 

LK2: 

 

 

 

6 - Relay N/O 

ON = Alarm manual reset 
OFF = Alarm auto reset

 

 

Connections (continued) 

 

Relay Mode 

 
All units are supplied in manual-reset mode. To convert to 
auto-reset  mode,  remove  the  link  LK2.  To  revert  back  to 
manual-reset replace the LK2 link. 

 

To reset an alarm, or after power failure, press the RESET 
button on the sensor lid. 
 

Dimensions 

 
 

 

 

 

 

 

LK1 
 
LK2 

VR2                 VR1 

160.9 mm

148.9 mm

67.
0 m

m

360.

0m

m

60.

0m

m

25.

0 m

m