Features 

Specification Product 

Codes 

• 

Damped or un-damped output 

• 

Manual or auto reset 

• 

Analogue output for service diagnostics 

Supply   

 

24Vac 50/60Hz or 24Vdc(-10 +15%) 

Power consumption 

62mA 

Outputs: 
 

Relay   

SPST 1A @ 24Vdc, 120Vac 

 Analogue 2-10Vdc 
Analogue status levels: 
 <2Vdc 

 Sensor 

fault 

 3-7Vdc 

 Normal 

operation 

 7-9Vdc 

 Optics 

require 

cleaning 

 >9.5Vdc Smoke 

alarm 

Minimum duct size 

100 x 320mm 

Maximum duct size 

450 x 450mm 

LED indication   

ON in alarm 

Reset   

 

Manual or auto reset, selectable  

Sensitivity 

 

3 to 25% obscuration, adjustable 

Signal damping  

On/Off selectable 

Housing: 
 

Dimensions 

130 x 68 x 58mm 

 Material 

 Glass-filled 

Polycarbonate to  

   UL94V-0  
Probe: 
 

Dimensions 

300 x 25.5mm dia. 

 Material 

 ABS 

plastic 

Protection 

 

IP65 (housing only) 

Ambient range: 
 

Temperature  +10 to 40°C 

 

RH 

 

0 to 95% non-condensing 

Country of origin 

UK 

 
 