Technical Overview 

The PS-24-24DC-E power supply is used to convert 24Vac to 
a regulated 24Vdc output offering advanced protection, self-
diagnostics and self-test facilities. Featuring over-current 
and over-voltage protection, LED indication of a wide range 
of conditions, an optional alarm relay output for loss of input 
and on-PCB reset button.  

 

 

 

      

It is intended for applications requiring auxiliary power for 
sensors or IO modules. 
 

Installation 

 
1.  The  PS-24-24DC-E should only be installed by a compe-

tent, suitably trained technician, experienced in installa-
tion with hazardous voltages. (>50Vac & <1000Vac or 
>75Vdc & 1500Vdc)  

 

 

 

 

 

2.  Ensure that all power is disconnected before carrying out 

any work on the  PS-24-24DC-E .   

 

 

 

 

3.  Maximum cable is 2.5mm², care must be taken not to 

over tighten terminals. 

 

 

 

 

 

4.  When mounting the  PS-24-24DC-E care should be taken 

not to stress the PCB when fitting to the DIN rail. If it is 
necessary remove the module from the DIN rail, be sure 
to use a flat bladed screwdriver to release the DIN clips. 

 

LED Indication 

 
Switch -On 
 
When the PSU is powered up, the LED shows solid orange 
for about 0.5 seconds. (If the reset button is pressed during 
power up, it holds the unit at this step.) After about 0.5 
seconds, the output is enabled and the alarm relay closes. 
This state is held for up to 5 seconds, or until the output 
voltage has achieved a minimum of 22.0Vdc. 
 
While the output voltage is within bounds, the relay is held 
closed, and the LED shows solid green. If the minimum 
voltage is not achieved, the output  is  turned  off,  and  the 
relay opens. The LED flashes long-short in orange until the 
reset button is pressed. 
 
Reset Button 
 
Whenever the reset button is pressed, the LED shows solid 
orange, the output is turned off and the relay is opened. 

 

LED Indication (continued)  

Output Out of Limits 
 
If the output voltage drops below 22.0Vdc, the LED flashes 
short-short in orange. The relay stays closed for a maximum 
of 4 seconds. If the output voltage is low enough for long 
enough, the output voltage is turned off, the relay opens, 
and the LED flashes long-short in orange until the reset 
button is pressed. If the output voltage rises above 25.0Vdc, 
the LED flashes short-short-short in red. The relay stays 
closed for a maximum of 1 second. If the output voltage is 
high enough for long enough, the output voltage is turned 
off, the relay opens, and the LED flashes long-short-short in 
red until the reset button is pressed. 
 

Connections 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
NB  The 0V terminal on the AC input connector is directly 
connected  
to the 0v terminal on the DC output connector. 
If the DC 0V terminal is connected to equipment which will 
earth this connection the 0V of the AC input will be 
earthed at the same time

Care should be taken to ensure that earthing the AC supply 
0V will not cause damage to any other equipment which 
may be powered from it. 
 

Neutral

 

 

Live 

AC INPUT 

DC OUTPUT 

0V 

0V 

 

+24Vdc 

+24Vdc 

Fuse 

Reset  

button      

Alarm  

output 

Status 

LED 

LED

1

 

N 24Vac L         Reset            Alarm 

+24Vdc         0V 